Trial Operation and Testing

1.

Trial operation and testing.

1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

For Heat pump

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temper-

ature.
1) Trial operation may be disabled in either mode depending on the room temperature.

Use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (26

°

C to 28

°

C in cooling mode, 20

°

C to 24

°

C in 

heating mode).

3) For protection, the system disables restart operation for 3 minutes after it is turned off.

For Cooling only

• Select the lowest programmable temperature.

1) Trial operation in cooling mode may be disabled depending on the room temperature.

Use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (26

°

C to 28

°

C).

3) For protection, the unit disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts, 

such as louver movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

2.

Test items.

Test Items

Symptom

(diagnostic display on RC)

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for interconnecting wire connections.

Inoperative or burn damage

Indoor or outdoor unit’s air intake or exhaust has clear path of air.
Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote control commands.

Inoperative

1) Press ON/OFF button to turn on the system.
2) Simultaneously press centor of TEMP button and MODE button.
3) Press MODE button twice.

(“    ” will appear on the display to indicate that Trial Operation mode is selected.)

4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press ON/OFF 

button.

Trial Operation from Remote Controller

01_EN_3P190114-1D.fm  Page 11  Monday, August 23, 2010  3:35 PM

Summary of Contents for FTXS50FV1B

Page 1: ...Espa ol Italiano Portugues T rk e Deutsch Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split sys...

Page 2: ...04 108 EC 3SB64526 5F Shinri Sada Manager Quality Control Department 25th of Nov 2009 DAIKIN TCF 015 M18 11 2009 FTKS50FV1B FTKS60FV1B FTKS71FV1B FTXS50FV1B FTXS60FV1B FTXS71FV1B FTX50GV1B FTX60GV1B F...

Page 3: ...mping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Insta...

Page 4: ...ted 2 Wireless remote controller 1 Turn on all the fluorescent lamps in the room if any and find the site where remote control signals are properly received by the indoor unit within 7 metres Installa...

Page 5: ...nd firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel 3 How to set the different addresses When two indoor units a...

Page 6: ...ounting plate should be installed on a wall which can support the weight of the indoor unit D E Remote controller holder Wireless remote controller Before screwing the remote controller holder to the...

Page 7: ...crews Recommended mounting plate retention spots and Dimensions 125 60 83 413 5 44 5 290 52 1050 99 5 52 90 55 100 100 Through the wall hole 80mm Drain hose position 80 80 Recommended mounting plate r...

Page 8: ...the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Installation tips 5 Pass the interconnecting wires from the outdoor unit through the feed through wall...

Page 9: ...late hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall Embedded Piping Follow the instructions given under 1 Insert the drain hose to this depth so it wont be pulled out of th...

Page 10: ...ck or fire 5 When connecting to an HA system 1 Remove the front grille 3 screws 2 Remove the electrical wiring box 1 screw 3 Remove the metal plate electrical wiring cover 4 tabs 4 Attach the connecti...

Page 11: ...oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do...

Page 12: ...nd liquid piping and to provide insulation dimen sions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pip...

Page 13: ...tioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If...

Page 14: ...1010 HT 3P190114 1D M06B094D Two dimensional bar code is a code for manufacturing 00_CV_3P190114 1D fm Page 2 Monday August 23 2010 3 29 PM...

Reviews: