9

English

Indoor Unit Installation

6.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) When drain hose requires extension, obtain an extension hose commercially avail-

able. 
Be sure to thermally insulate the indoor section of the extension hose.

4) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available 
drain socket (nominal diameter 13mm) as a 
joint.

Refrigerant Piping Work

, install as described in the installation manual supplied with the Multi outdoor unit.

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

φ

18

Extension drain hose

Heat insulation tube
(Field supply)

Drain hose supplied with 
the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

φ

18

With a Multi indoor unit

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

01_EN_3P190114-1D.fm  Page 9  Monday, August 23, 2010  3:35 PM

Summary of Contents for FTXS50FV1B

Page 1: ...Espa ol Italiano Portugues T rk e Deutsch Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split sys...

Page 2: ...04 108 EC 3SB64526 5F Shinri Sada Manager Quality Control Department 25th of Nov 2009 DAIKIN TCF 015 M18 11 2009 FTKS50FV1B FTKS60FV1B FTKS71FV1B FTXS50FV1B FTXS60FV1B FTXS71FV1B FTX50GV1B FTX60GV1B F...

Page 3: ...mping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Insta...

Page 4: ...ted 2 Wireless remote controller 1 Turn on all the fluorescent lamps in the room if any and find the site where remote control signals are properly received by the indoor unit within 7 metres Installa...

Page 5: ...nd firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel 3 How to set the different addresses When two indoor units a...

Page 6: ...ounting plate should be installed on a wall which can support the weight of the indoor unit D E Remote controller holder Wireless remote controller Before screwing the remote controller holder to the...

Page 7: ...crews Recommended mounting plate retention spots and Dimensions 125 60 83 413 5 44 5 290 52 1050 99 5 52 90 55 100 100 Through the wall hole 80mm Drain hose position 80 80 Recommended mounting plate r...

Page 8: ...the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Installation tips 5 Pass the interconnecting wires from the outdoor unit through the feed through wall...

Page 9: ...late hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall Embedded Piping Follow the instructions given under 1 Insert the drain hose to this depth so it wont be pulled out of th...

Page 10: ...ck or fire 5 When connecting to an HA system 1 Remove the front grille 3 screws 2 Remove the electrical wiring box 1 screw 3 Remove the metal plate electrical wiring cover 4 tabs 4 Attach the connecti...

Page 11: ...oil from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do...

Page 12: ...nd liquid piping and to provide insulation dimen sions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pip...

Page 13: ...tioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If...

Page 14: ...1010 HT 3P190114 1D M06B094D Two dimensional bar code is a code for manufacturing 00_CV_3P190114 1D fm Page 2 Monday August 23 2010 3 29 PM...

Reviews: