3
|
Components
Service manual
84
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
3.7 Main PCB
3.7.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
ARXP-L + ARXP-M + RXP-L + RXP-M + RXP50~71N units
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Measure the voltage between the black and white wires.
Result:
The measured voltage MUST be 230 V AC.
a
b
a
Black wire
b
White wire
Is the measured voltage on the PCB
correct?
Action
Yes
84] of the PCB and
continue with the next procedure.
No
Continue with the next step.
3
Check the power supply to the unit, see
Does the unit receive power?
Action
Yes
96].
No
Adjust the power supply to the unit, see
143].
ARXP20~35N + RXP20~35N units
Prerequisite:
Stop the unit operation via the user interface.