background image

5 Installation

Installation manual

6

ATXM20~50+FTXM20~71N2V1B

Daikin room air conditioner

3P482320-8K – 2018.09

i

Outline of back side

j

Outline of front side

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  (class  15~42)  or  80  mm  (class  50~71)  large
feed-through  hole  in  the  wall  with  a  downward  slope  towards
the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65/80

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.2.3

To remove the pipe port cover

To  connect  the  piping  on  right-side,  right-bottom,  left-side  or  left-
bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.2.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Rigid polyvinyl chloride pipe.

 When connecting a rigid polyvinyl

chloride pipe (nominal Ø13 mm) directly to the drain hose as with
embedded piping work, use a field supplied drain socket (nominal
Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Rigid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

≥50

mm

Summary of Contents for FTXM20N2V1B

Page 1: ...kin room air conditioner English Installation manual Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50N2V1B FTXM60N2V1B FTXM71N2V1B ...

Page 2: ...condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че с...

Page 3: ...ference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Pap...

Page 4: ...tallation 5 1 Opening the indoor unit 5 1 1 To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Panel tabs 2 Remove the front panel by sliding it to the left or the right and pulling it toward you Result The front panel shaft on 1 side will be disconnected 3 Disconnect the front panel shaft on the other side in the same manner a a Front panel shaft 5 1 ...

Page 5: ... Finish the installation by securing the mounting plate on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate pocket Class 15 42 337 810 A 294 44 5 170 68 68 44 5 137 137 337 50 213 237 170 A d e mm a a f h g a a b a c a c a d e Class 50 71 A 990 1040 300 170 60 170 52 52 122 126 5 48 60 435 447 PIPING HOLE CE...

Page 6: ...r as this would damage the front grille 5 2 4 To provide drainage Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the indoor unit Checking for water leaks General guidelines Pipe length Keep drain piping as short as possible Pipe size If drain hose extension or embedded drain piping is required use appropriate parts that match ...

Page 7: ... drain leakage from the plug a a 4 mm hexagonal wrench 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left back piping C Left bottom piping a Remove the ...

Page 8: ...apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or ...

Page 9: ...o the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 5 6 2 To install the wireless LAN adapter on page 9 Basic parameters What Value Frequency range 2400 MHz 2483 5 MHz Radio protocol IEEE 802 11b g n Radio frequency channel 1 11 Output power 0 dBm 18 dBm Effective radiated power 17 dBm 11b 13 dBm 11g 12 dBm 11n...

Page 10: ...essory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the installation steps in reverse order For class 50 71 1 Place the wireless LAN adapter into the holder 2 Press down on the adapter to fix it in the holder 3 To remove the adapter bend one clamp of the ho...

Page 11: ...nts in the switch box The insulation resistance of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 6 2 To perform a test run Prerequisite Power supply MUST be in ...

Page 12: ...TCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR M...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P482320 8K 2018 09 Copyright 2018 Daikin ...

Reviews: