ESIE16-02K
|
Part 2. Troubleshooting
2.4. Component checklist
Page 54
31/05/21
|
Version 1.1
RA R32 Split & multi split M-Series
7. Megger the compressor using 500 or 1000 VDC, the insulation must be higher than 3 M
Ω
.
8. Replace the compressor if the windings and/or insulation measurements fail (refer to
"Replacing compressor" on page 77
9. Run the compressor and measure the current in each phase; the current for each phase should be identical (refer to
specific information" on page 129
). In that case it can be decided to preventively replace the compressor (refer to