Part 2. Troubleshooting
2.3. Symptom based troubleshooting
Page 44
31/05/21
|
Version 1.1
RA R32 Split & multi split M-Series
2.3. Symptom based troubleshooting
2.3.1. Operation does not start
2.3.2. Operation sometimes stops
Check
Detail
When the operation lamp is off, there is a power failure.
Check the power supply.
Is the power supply breaker ON?
Do other electrical appliances work?
Is the rated voltage (± 10%) supplied?
Check the insulation of the electric system.
Check the type of the indoor units.
Is the indoor unit type compatible with the outdoor unit?
Check the transmission between indoors and outdoor.
Connection wires.
Check the outdoor temperature.
Heating operation cannot be used when the outdoor temperature
is 18°C WB or higher.
Cooling operation cannot be used when the outdoor temperature
is below 10°C DB.
When the operation lamp blinks, there may be an error code,
activating the protection device.
Diagnose with remote controller indication.
See
"Error based troubleshooting" on page 20
Check the remote controller addresses.
Are the address settings for the remote controller and indoor unit
correct?
Check the operation circuit.
Is the thermal fuse blown.
Are wire size and wire connections OK?
Check fan motor.
Is the magnetic switch defective?
Is the overcurrent relay defective?
Check compressor.
Is the contact defective?
Is the protection thermostat defective?
Is the compressor itself defective?
Check remote controller.
Are the batteries LOW?
Are there incorrect settings?
Check the LEDs on outdoor unit PCB2 (3MXM-N(9),
4MXM-N(9),5MXM-N(9)).
See
"Error codes via outdoor unit PCB2 (Service PCB)
(3MXM-N(9), 4MXM-N(9), 5MXM-N(9))" on page 19
Check
Detail
When the operation lamp is off, there is a power failure.
Check the power supply.
A power failure of 2 to 10 cycles stops air conditioner operation.
Check the outdoor temperature.
Heating operation cannot be used when the outdoor temperature
is 18°C WB or higher.
Cooling operation cannot be used when the outdoor temperature
is below 10°C DB.
When the operation lamp blinks, there may be an error code,
activating the protection device.
Diagnose with remote controller indication.
See
"Error based troubleshooting" on page 20
Check the LEDs on outdoor unit PCB2 (3MXM-N(9),
4MXM-N(9),5MXM-N(9)).
See
"Error codes via outdoor unit PCB2 (Service PCB)