6 Piping installation

Installation manual

6

FTXF50~71D5V1B6

Split system air conditioners

3P512025-11Z – 2021.10

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Pipe outer diameter (mm)

Liquid piping

Gas piping

Ø6.4

Ø12.7

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

6.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

6.2.1

To connect the refrigerant piping to the
indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

1

Connect refrigerant piping to the unit using 

flare connections

.

2

Insulate 

the  refrigerant  piping,  interconnection  cable  and  drain

hose on the indoor unit as follows:

c

a

b

f

d

g

e

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

g

Drain hose

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

7

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

Summary of Contents for FTXF50D5V1B6

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FTXF50D5V1B6 FTXF60D5V1B6 FTXF71D5V1B6...

Page 2: ...ers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons WARNING Make sure installati...

Page 3: ...ds or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing cap...

Page 4: ...perating gas appliance or an operating electric heater The room size shall be as specified in the General safety precaution 5 1 1 Installation site requirements of the indoor unit INFORMATION The soun...

Page 5: ...TION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Attach the drain hose with adhesive vinyl tape to the bottom...

Page 6: ...2 7 mm 1 2 a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might be required 6 1 2 Refrigerant piping...

Page 7: ...aller reference guide for opening procedure 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Not...

Page 8: ...g through the wall hole and seal the gap with a putty 8 3 To fix the unit on the mounting plate 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide 2 Press the bottom frame of t...

Page 9: ...he system stops operating 3 minutes after the unit is turned OFF 9 2 1 To perform a test run in winter season When operating the air conditioner in Cooling mode in winter set it to test run operation...

Page 10: ...tepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation P...

Page 11: ......

Page 12: ...suyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe stanbul T RK YE Factory Kargal hanbaba OSB Mahallesi Organize Sanayi 1 Sokak No 28 54300 Hendek Sakarya T RK YE 3P512025 11Z 2021 10...

Reviews: