background image

3 About the box

Installation manual

3

FTXF50~71D5V1B6
Split system air conditioners
3P512025-11Z – 2021.10

Piping installation (see 

"6 Piping installation"

 [

4

 6])

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

DANGER: RISK OF BURNING/SCALDING

NOTICE

▪ Use the flare nut fixed to the unit.

▪ To prevent gas leakage, apply refrigeration oil ONLY to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

NOTICE

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

NOTICE

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

Electrical installation (see 

"7 Electrical installation"

 [

4

 6])

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

WARNING

Improper  installation  or  attachment  of  equipment  or
accessories  could  result  in  electrical  shock,  short-circuit,
leaks,  fire  or  other  damage  to  the  equipment.  ONLY  use
accessories,  optional  equipment  and  spare  parts  made  or
approved by Daikin.

3

About the box

3.1

Indoor unit

INFORMATION

The  following  figures  are  just  examples  and  may  NOT
completely match your system layout.

▪ At delivery, the unit MUST be checked for damage. Any damage

MUST be reported immediately to the claims agent of the carrier.

▪ Bring  the  packed  unit  as  close  as  possible  to  its  final  installation

position to prevent damage during transport.

3.1.1

To remove the accessories from the
indoor unit

1

Remove the accessories located at the bottom of the package.

e

d

b

a

c

f

g

h

i

j

a

Installation manual

b

Operation manual

c

General safety precautions

d

Indoor unit fixing screw (M4×12L). Refer to 

"8.3 To fix the

unit on the mounting plate"

 [

4

 8].

e

Dry battery AAA.LR03 (alkaline) for user interface

f

User interface holder

g

User interface

h

Mounting plate

j

Energy label

Summary of Contents for FTXF50D5V1B6

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FTXF50D5V1B6 FTXF60D5V1B6 FTXF71D5V1B6...

Page 2: ...ers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons WARNING Make sure installati...

Page 3: ...ds or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing cap...

Page 4: ...perating gas appliance or an operating electric heater The room size shall be as specified in the General safety precaution 5 1 1 Installation site requirements of the indoor unit INFORMATION The soun...

Page 5: ...TION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Attach the drain hose with adhesive vinyl tape to the bottom...

Page 6: ...2 7 mm 1 2 a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might be required 6 1 2 Refrigerant piping...

Page 7: ...aller reference guide for opening procedure 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Not...

Page 8: ...g through the wall hole and seal the gap with a putty 8 3 To fix the unit on the mounting plate 1 Set the indoor unit on the mounting plate hooks Use the marks as a guide 2 Press the bottom frame of t...

Page 9: ...he system stops operating 3 minutes after the unit is turned OFF 9 2 1 To perform a test run in winter season When operating the air conditioner in Cooling mode in winter set it to test run operation...

Page 10: ...tepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation P...

Page 11: ......