1-12
ELECTRICAL WIRING CONNECTION
IMPORTANT :
* The figures shown in the table are for information purpose only. They should be checked and selected
to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Model
Indoor (FTXC)
25
35
50
60
Outdoor (RXC)
25
35
50
60
Voltage range**
220-240V/~/50Hz +
!
Power supply cable size* mm
2
Number of conductors
1.5
3
2.5
3
Interconnection cable size* mm
2
Number of conductors
1.5
4
2.5
4
Recommended fuse /circuit breaker rating A
16
20
All wires must be firmly connected.
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly fixed to avoid any gap.
Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
•
•
•
•
•
•
•
Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
•
•
•
•
Attach insulation sleeve
Round crimp-style terminal
Electric wire
Connect wires of the
same gauge to both side.
Do not connect wires of the
same gauge to one side.
Do not connect wires
of different gauges.
SIG
Power supply
terminal block
Use the specified wire type
and connect it securely.
Firmly secure wire retainer so wire
terminations will not receive external stress.
Shape wires so
that the service
lid and stop
valve cover fit
securely.
Inverter (Power Outdoor)
2
SIG
1
Outdoor Unit
Terminal Block
Indoor Unit
Terminal Block
2
SIG
1
Interconnection
cable
N
L
N / L2
L / L1
Power
Supply
Main
Switch
Fuse / Circuit
Breaker
Power Supply Cable
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
!
1 IM-3WMYJ(R)-0816(0)-DAIKIN-EN-12 12
1 IM-3WMYJ(R)-0816(0)-DAIKIN-EN-12 12
12/22/16 10:23:28 AM
12/22/16 10:23:28 AM
Summary of Contents for FTXC25AV1B
Page 2: ......
Page 123: ...7 1 XEMA A MEP K FTXC C B A...
Page 126: ...7 4 H MAH E CTOPO HO 1 1 OFF H MAH E Xm2 13...
Page 128: ...2 K a B 25 35 K M4 x 12L e 75 50 500 1200 50 100 50 50 100 150 150 300 50 1200 1 2 3 7 6...
Page 129: ...1 2 30 3 16 50 60 H A B C D 300 1000 300 500 2 A A 7 7 C D pe c pe c A B H 2 H...
Page 130: ...50 50 75 c y ox 7 8...
Page 136: ...7 14 R32 13 25 OFN...
Page 137: ...7 15 C 3 30 760 760mmHg 3 2 4 o 3 760 760 3 3...
Page 140: ...7 18 FRONT K a B 2 1 4 2 5 4 3 K a CTOPO HO 1 3 2 4...
Page 141: ...7 19 2 1 2 c 3 40 104 F 1 2 3 1 2 40 104 F 1 2 1 2 CTOPO HO...
Page 142: ...7 20 3 1 3 4 2 3 4 5 6 2 30 C 86 F CTOPO HO 40 C...
Page 143: ...8 1 FTXC C B A...
Page 146: ...8 4 1 1 ON OFF OFF Xm2 13...
Page 149: ...16mm 50 60 H A B C D mm 300 1000 300 500 2 A 1 2 30mm 3 8 7 C D A B H 2 H...
Page 150: ...50 50 75 mm 8 8...
Page 156: ...R32 LFL 13 25 OFN OFN OFN OFN 8 14...
Page 157: ...8 15 3 30 760mmHg 760 mmHg 3 2 4 mm 3 760 mmHg 760mmHg 3 3...
Page 161: ...8 19 2 1 2 3 40 C 104 F 1 2 3 2 40 C 104 F 1 2 2...
Page 162: ...8 20 3 1 3 4 2 3 4 5 6 2 30 C 86 F 40 C...
Page 163: ...MEMO PROMEMORIA MITTEILUNG EL MEMOR NDUM LE M MO NOT...
Page 167: ......