8 Finishing the indoor unit installation

Installation manual

9

CTXA-C(W)(B)(S) + FTXA-C(W)(B)(S)
Daikin room air conditioner
3P697375-6B – 2023.05

a

a

S21 connector

3

Put  the  electrical  wiring  box  cover  back  and  pull  the  wire
harness around it as shown in the figure above.

8

Finishing the indoor unit
installation

8.1

To insulate the drain piping,
refrigerant piping and
interconnection cable

f

g
h

a

b

c
d

e

a

Slit

b

Heat insulation pipe cover

c

Liquid pipe

d

Gas pipe

e

Drain pipe

f

Interconnection wire

g

Insulation tape

h

Vinyl tape

1

After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap refrigerant piping, interconnection cable and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant piping

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

8.2

To pass the pipes through the wall
hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

c

c

d

e

a

b

a

Drain hose

b

Caulk this hole with putty or caulking material

c

Adhesive vinyl tape

d

Insulation tape

e

Mounting plate (accessory)

NOTICE

▪ Do NOT bend refrigerant pipes.

▪ Do  NOT  push  the  refrigerant  pipes  onto  the  bottom

frame or the front grille.

2

Pass the drain hose and refrigerant piping through the wall hole
and seal the gap with a putty.

8.3

To fix the unit on the mounting
plate

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

2

Press the bottom frame of the unit with both hands to set it on
the  bottom  hooks  of  the  mounting  plate.  Make  sure  that  the
wires do NOT get squeezed anywhere.

Note: 

  Take  care  that  the  interconnection  cable  does  NOT  get

caught in the indoor unit.

3

Press the bottom edge of the indoor unit with both hands until it
is firmly caught by the mounting plate hooks.

4

Secure the indoor unit to the mounting plate using 2 indoor unit
fixing screws M4×12L (accessory).

9

Configuration

INFORMATION

In case 2 indoor units are installed in 1 room, set different
addresses for 2 user interfaces. For procedure refer to the
installer  reference  guide,  for  location  see 

"1.1  About  this

document"

 [

4

 2].

Summary of Contents for FTXA25C2V1BW

Page 1: ...manual Daikin room air conditioner CTXA15C2V1BW FTXA20C2V1BW FTXA25C2V1BW FTXA35C2V1BW FTXA42C2V1BW FTXA50C2V1BW CTXA15C2V1BS FTXA20C2V1BS FTXA25C2V1BS FTXA35C2V1BS FTXA42C2V1BS FTXA50C2V1BS CTXA15C2V...

Page 2: ...less remote control 10 11 Disposal 10 12 Technical data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document WARNING Make sure installati...

Page 3: ...cured on site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthin...

Page 4: ...E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause fa...

Page 5: ...h h b e c a a a a a a a Recommended mounting plate fixing spots h Hole for embedded piping 65 mm b Pocket for the pipe port cover i Value for tape measure c Liquid pipe end j Position for tape measure...

Page 6: ...n left side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insula...

Page 7: ...MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible 1 Connect refrigerant piping to the unit using flare connection...

Page 8: ...distance between both wirings should ALWAYS be at least 50 mm Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of prac...

Page 9: ...along the pipe path marking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE D...

Page 10: ...ide of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully...

Page 11: ...R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number...

Page 12: ...3P697375 6B 2023 05 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: