background image

6 Piping installation

Installation manual

6

CTXA-C(W)(B)(S) + FTXA-C(W)(B)(S)

Daikin room air conditioner

3P697375-6B – 2023.05

5.2.3

To remove the pipe port cover

INFORMATION

To  connect  the  piping  on  right-side,  right-bottom,  left-side
or left-bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.3

Connecting the drain piping

5.3.1

To connect the piping on right side, right-
back, or right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.

2

Wrap  the  drain  hose  and  the  refrigerant  pipes  together  using
insulation tape.

A

B

a b

A

Right-side piping

B

Right-bottom piping

C

Right-back piping

a

Remove the pipe port cover here for right side piping

b

Remove the pipe port cover here for right-bottom piping

5.3.2

To connect the piping on left side, left-
back, or left-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

Summary of Contents for FTXA25C2V1BW

Page 1: ...manual Daikin room air conditioner CTXA15C2V1BW FTXA20C2V1BW FTXA25C2V1BW FTXA35C2V1BW FTXA42C2V1BW FTXA50C2V1BW CTXA15C2V1BS FTXA20C2V1BS FTXA25C2V1BS FTXA35C2V1BS FTXA42C2V1BS FTXA50C2V1BS CTXA15C2V...

Page 2: ...less remote control 10 11 Disposal 10 12 Technical data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document WARNING Make sure installati...

Page 3: ...cured on site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthin...

Page 4: ...E g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause fa...

Page 5: ...h h b e c a a a a a a a Recommended mounting plate fixing spots h Hole for embedded piping 65 mm b Pocket for the pipe port cover i Value for tape measure c Liquid pipe end j Position for tape measure...

Page 6: ...n left side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insula...

Page 7: ...MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible 1 Connect refrigerant piping to the unit using flare connection...

Page 8: ...distance between both wirings should ALWAYS be at least 50 mm Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of prac...

Page 9: ...along the pipe path marking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE D...

Page 10: ...ide of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully...

Page 11: ...R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number...

Page 12: ...3P697375 6B 2023 05 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: