background image

13

English

Trial Operation and Testing

1.

Trial operation and testing

• Trial operation should be carried out in either COOL or HEAT operation.

1-1. Measure the supply voltage and make sure that it is within the specified range.
1-2. In COOL operation, select the lowest programmable temperature; in HEAT operation, 

select the highest programmable temperature.

1-3. Carry out the trial operation in accordance with the operation manual to ensure that all

functions and parts, such as flap movement, are working properly.

• For protection, the system disables restart operation for 3 minutes after it is turned off.

1-4. After trial operation is complete, set the temperature to a normal level (26°C to 28°C in 

COOL operation, 20°C to 24°C in HEAT operation).

• When operating the air conditioner in COOL operation in winter, set it to the trial operation mode using the following 

method.

1) Press

and

at the same time.

2) Press

, select

, press

.

3) Press

or

to turn on the system.

• Trial operation will stop automatically after about 30 minutes.

To stop the operation, press

.

• Some of the functions cannot be used in the trial operation mode.

• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some time after

installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode 

when the circuit breaker is opened again.

2.

Test items 

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet are unobstructed

Incomplete cooling/heating function

Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote control commands.

No operation

3PEN393185-5J.book  Page 13  Friday, October 23, 2015  8:22 AM

Summary of Contents for FTX50KMV1B

Page 1: ...eutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycck rk e MODELS FTX50KMV1B FTX60KMV1B FTX71KMV1B Installation manual Installationsanleitung Manuel d installation Installatiehandleiding Manua...

Page 2: ......

Page 3: ...nte por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de a...

Page 4: ...pecified parts may result in the unit falling water leakage electric shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insuff...

Page 5: ...running and the stop valve is open during pump down air will be sucked in when the refrigerant piping is removed causing abnormal pressure in the refrigeration cycle which may result in equipment dama...

Page 6: ...tion gloves Place both hands under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2...

Page 7: ...shown in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring covers 1 Remove the front grille...

Page 8: ...ow to remove the indoor unit Push up the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front pa...

Page 9: ...ert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant p...

Page 10: ...e markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through t...

Page 11: ...nto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tight...

Page 12: ...R T THERMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDE YOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS...

Page 13: ...tarburst connections as they may cause overheating electri cal shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the te...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...igerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insul...

Page 16: ...y after about 30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the syste...

Page 17: ......

Page 18: ...3P393185 5J 2015 10 Copyright 2015 Daikin...

Reviews: