Refrigerant Piping Work

2.

Refrigerant piping

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. 

2-1. Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

2-2. Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 12.7mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm min.

30mm or more

Thickness 0.8mm (C1220T-O)

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

Piping union

Flare nut

Spanner

[Tighten]

1/4 inch

1/2 inch

Torque wrench

Flare nut tightening torque

Gas side

49.5-60.3N • m

(505-615kgf • cm)

14.2-17.2N • m

(144-175kgf • cm)

Liquid side

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt 
or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Inter-unit wire

Liquid pipe

Drain hose

Finishing tape

Gas pipe 

insulation

Liquid pipe 

insulation

3PEN393185-5J.book  Page 12  Friday, October 23, 2015  8:22 AM

Summary of Contents for FTX50KMV1B

Page 1: ...eutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycck rk e MODELS FTX50KMV1B FTX60KMV1B FTX71KMV1B Installation manual Installationsanleitung Manuel d installation Installatiehandleiding Manua...

Page 2: ......

Page 3: ...nte por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de a...

Page 4: ...pecified parts may result in the unit falling water leakage electric shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insuff...

Page 5: ...running and the stop valve is open during pump down air will be sucked in when the refrigerant piping is removed causing abnormal pressure in the refrigeration cycle which may result in equipment dama...

Page 6: ...tion gloves Place both hands under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2...

Page 7: ...shown in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring covers 1 Remove the front grille...

Page 8: ...ow to remove the indoor unit Push up the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front pa...

Page 9: ...ert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant p...

Page 10: ...e markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through t...

Page 11: ...nto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tight...

Page 12: ...R T THERMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDE YOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS...

Page 13: ...tarburst connections as they may cause overheating electri cal shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the te...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...igerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insul...

Page 16: ...y after about 30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the syste...

Page 17: ......

Page 18: ...3P393185 5J 2015 10 Copyright 2015 Daikin...

Reviews: