Indoor Unit Installation

5.

Drain piping

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

4) When extending the drain hose, use a commercially available 

extension hose with an inner diameter of 16mm. Be sure to 
thermally insulate the indoor section of the extension hose.

5) When connecting a rigid polyvinyl chloride pipe (nominal 

diameter 13mm) directly to the drain hose attached to the 
indoor unit as with embedded piping work, use any 
commercially available drain socket (nominal diameter 
13mm) as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward so 

that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

Extension drain hose

Heat insulation tube 
(field supply)

Drain hose supplied 
with the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

Drain hose supplied 
with the indoor unit

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

3PEN393185-5J.book  Page 11  Friday, October 23, 2015  8:22 AM

Summary of Contents for FTX50KMV1B

Page 1: ...eutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycck rk e MODELS FTX50KMV1B FTX60KMV1B FTX71KMV1B Installation manual Installationsanleitung Manuel d installation Installatiehandleiding Manua...

Page 2: ......

Page 3: ...nte por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de a...

Page 4: ...pecified parts may result in the unit falling water leakage electric shocks or fire Install the air conditioner on a foundation strong enough to withstand the weight of the unit A foundation of insuff...

Page 5: ...running and the stop valve is open during pump down air will be sucked in when the refrigerant piping is removed causing abnormal pressure in the refrigeration cycle which may result in equipment dama...

Page 6: ...tion gloves Place both hands under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2...

Page 7: ...shown in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring covers 1 Remove the front grille...

Page 8: ...ow to remove the indoor unit Push up the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front pa...

Page 9: ...ert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant p...

Page 10: ...e markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through t...

Page 11: ...nto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tight...

Page 12: ...R T THERMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDE YOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS...

Page 13: ...tarburst connections as they may cause overheating electri cal shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the te...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...igerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insul...

Page 16: ...y after about 30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the syste...

Page 17: ......