Indoor Unit Installation

CAUTION

When connecting the connection wire to the terminal block using a single core wire, 
be sure to perform curling. 
Problems with the installation may cause heat and fires. 

1) As shown in the illustration on the right-hand side, insert the 

wires including the ground wire into the conduit and secure 
them with lock nut onto the conduit mounting plate.

2) Insert the wires including the ground wire into 

 tube.

3) Strip wire ends (9/16 inch (15mm)).

4) Match wire colors with terminal numbers on indoor and outdoor 

unit’s terminal blocks and firmly screw wires to the 
corresponding terminals.

5) Connect the ground wires to the corresponding terminals.
6) Pull the wires and check that the wires are securely fixed to the 

terminal block.

7) In case of connecting to an adapter system, run the remote 

controller cable and attach the S21. 
(Refer to 

“4. When connecting to an HA system” 

on page 9.)

8) Shape the wires so that the service lid fits securely, then close service lid.

5.

Drain piping 

1) Connect the drain hose, as described on the right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly. 

3) If drain hose extension or embedded drain piping is required, use appropriate parts 

that match the hose front end.

Figure of hose front end

• When drain hose requires extension, obtain an extension 

hose with an inner diameter of 5/8 inch (16mm). 
Be sure to thermally insulate the indoor section of the 
extension hose.

• When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 1/2 inch (13mm)) directly to 
the drain hose attached to the indoor unit as with 
embedded piping work, use any commercially 
available drain socket (nominal diameter 1/2 inch 
(13mm)) as a joint. 

Good

Wrong

Conduit 

mounting plate

Lock nut

Back

Conduit 

Terminal block

Electrical wiring box

Use the specified wire type.

Wire retainer

Shape wires so that 

the service lid will fit 

securely.

Tube

K

K

1

2

3

1 2 3

L

1

L

2

Wire size and length must 

comply with local codes.

Firmly fix the wires with 

the terminal screws.

Outdoor

unit

Indoor 

unit

Firmly fix the wires with the terminal screws.

The drain hose should 

be inclined downward.

No trap is permitted.

Do not put the end 

of the hose in water.

ϕ

11/16” (

ϕ

18mm)

ϕ

5/8” (

ϕ

16mm)

Indoor unit 

drain hose

Extension drain hose

Heat insulation tube (field supply)

ϕ

5/8” (

ϕ

16mm)

Drain hose supplied 

with the indoor unit

Commercially available 

drain socket 

(nominal diameter 1/2 inch 

(13mm))

Commercially available 

rigid polyvinyl chloride pipe

(nominal diameter 1/2 inch 

(13mm))

Drain hose supplied with 

the indoor unit

ϕ

11/16” (

ϕ

18mm)

01_EN_3P457790-1.fm  Page 7  Thursday, December 1, 2016  3:51 PM

Summary of Contents for FTX30NVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Français Español MODELS FTX30NVJU FTX36NVJU Installation manual Manuel d installation Manual de instalación ...

Page 2: ...leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transportation materials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood parts including plastic packing materials used for transportation may...

Page 3: ...nted from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and foll...

Page 4: ...quipment is nearby 2 Wireless remote controller 1 Turn on all the fluorescent lamps in the room if any and find a location where the remote controller signals are properly received by the indoor unit within 23ft 7m 2 Configure the jumper Configure according to the type of unit heat pump or cooling only the user purchased The default setting is heat pump For heat pump outdoor unit model RX No chang...

Page 5: ...ters The service lid is removable Opening method 1 Remove the service lid screws 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down Service lid Bottom of indoor unit Front grille fixture Screw covers 3 J Remote controller holder fixing screws M3 13 16 M3 20mm 2 F C Titanium apatite photocatalytic air purifying filter 3 Titanium apatite photocatalytic air purifying...

Page 6: ...using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Service lid on page 4 5 Pass the inter unit wire from the outdoor unit through the feed through wall hole and then through the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the inter unit wire ends are to be...

Page 7: ...c shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire 3 Switch around the drain hose and drain plug 1 Remove the fixing screw and pull out the drain hose How to switch a...

Page 8: ... embedded drain piping is required use appropriate parts that match the hose front end Figure of hose front end When drain hose requires extension obtain an extension hose with an inner diameter of 5 8 inch 16mm Be sure to thermally insulate the indoor section of the extension hose When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly to the drain hose attached to...

Page 9: ...thylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Be sure to use insulation that is designed for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Piping size Minimum bend radius Piping thic...

Page 10: ...hen mount the front panel 3 How to set the different addresses When 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not to damage any of the surrounding parts 1 Remove the front grille 6 screws 3 front grille fixtures 2 Remove the metal plate electrical ...

Page 11: ... breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and outdoor units are installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling heating function Refrigerant g...

Page 12: ... 1611 HT M16B117 The two dimensional bar code is a manufacturing code 3P457790 1 ...

Reviews: