Indoor Unit Installation

1.

Installing the mounting plate

The mounting plate should be installed on a wall which can support the weight of the indoor unit.

1)Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the drilling points 

on the wall.

2)Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions 

2.

Drilling a wall hole and installing wall embedded pipe

WARNING

For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole to 
prevent possible heat, electric shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to 

prevent condensation. 

1) Drill a feed-through hole with a 

3-1/8 inch (80mm) diameter 

through the wall at a downward angle toward the outside.

2) Insert a wall embedded pipe into the hole.

3) Insert a wall hole cover into wall pipe.

4) After completing refrigerant piping, wiring, and drain piping, caulk 

the pipe hole gap with putty.

3.

Installing the indoor unit

3-1. Right-side, right-back, or right-bottom piping 

1) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with 

an insulation tape. 

3) Pass the drain hose and refrigerant pipes through the wall hole, 

then position the indoor unit on the 

 mounting plate hooks, 

using the 

 markings at the top of the indoor unit as a guide. 

4) Open the front panel, then open the service lid. 

(Refer to 

“Service lid”

 on page 4.)

5) Pass the inter-unit wire from the outdoor unit through the feed-through wall hole and 

then through the back of the indoor unit. Pull them through the front side. Bend the 
ends of tie wires upward for easier work in advance. (If the inter-unit wire ends are to 
be stripped first, bundle wire ends with adhesive tape.) 

6) Press the bottom frame of the indoor unit with both hands until it is firmly caught by 

the 

 mounting plate hooks. Make sure that the wires do not catch on the edge of the indoor unit.

unit: inch (mm)

φ

3-1/8

(

φ

80)

7-1/2 (190)

2-1/16 (53)

5-1/4

(134)

5-3/16

(131)

1-3/4 (45)

1-3/4 (45)

13-3/8 (340)

2-9/16

(65)

φ

3-1/8

(

φ

80)

6-5/16

(161)

7-3/16

(183)

3-1/2

(89)

47-1/4 (1200)

1-7/8

(47)

21-13/16 (554)

Use a tape 

measure 

as shown.

Position 

the end of 

a tape 

measure 

at 

∇.

Gas pipe end 

Liquid pipe end

Place the pipe port cover in this pocket.

Through-the-wall hole 

φ

3-1/8 inch (

φ

80mm)

Drain 

hose 

position

Removed pipe 

port cover 

A

Mounting 

plate

  The removed pipe port 

cover can be kept in the 

mounting plate pocket.

Recommended mounting plate 

retention spots (9 spots in all)

(Bolt size: 3/8” (M10))

(Bolt size: 3/8” (M10))

(Bolt size: 3/8” (M10))

Place a leveler on raised tab.

Inside

Outside

Caulking

(field supply)

Wall embedded pipe 

(field supply)

Wall hole cover

(field supply)

φ

3-1/8”

(80mm)

Right-

bottom 

piping

Right-back piping

Bind refrigerant pipe 

and drain hose together 

with adhesive vinyl tape.

Remove pipe port 

cover here for 

right-side piping.

Remove pipe port 

cover here for 

right-bottom piping.

A

Mounting plate

A

A

01_EN_3P457790-1.fm  Page 5  Thursday, December 1, 2016  3:51 PM

Summary of Contents for FTX30NVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Français Español MODELS FTX30NVJU FTX36NVJU Installation manual Manuel d installation Manual de instalación ...

Page 2: ...leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transportation materials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood parts including plastic packing materials used for transportation may...

Page 3: ...nted from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and foll...

Page 4: ...quipment is nearby 2 Wireless remote controller 1 Turn on all the fluorescent lamps in the room if any and find a location where the remote controller signals are properly received by the indoor unit within 23ft 7m 2 Configure the jumper Configure according to the type of unit heat pump or cooling only the user purchased The default setting is heat pump For heat pump outdoor unit model RX No chang...

Page 5: ...ters The service lid is removable Opening method 1 Remove the service lid screws 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down Service lid Bottom of indoor unit Front grille fixture Screw covers 3 J Remote controller holder fixing screws M3 13 16 M3 20mm 2 F C Titanium apatite photocatalytic air purifying filter 3 Titanium apatite photocatalytic air purifying...

Page 6: ...using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Service lid on page 4 5 Pass the inter unit wire from the outdoor unit through the feed through wall hole and then through the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the inter unit wire ends are to be...

Page 7: ...c shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire 3 Switch around the drain hose and drain plug 1 Remove the fixing screw and pull out the drain hose How to switch a...

Page 8: ... embedded drain piping is required use appropriate parts that match the hose front end Figure of hose front end When drain hose requires extension obtain an extension hose with an inner diameter of 5 8 inch 16mm Be sure to thermally insulate the indoor section of the extension hose When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly to the drain hose attached to...

Page 9: ...thylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Be sure to use insulation that is designed for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid refrigerant pipes Piping size Minimum bend radius Piping thic...

Page 10: ...hen mount the front panel 3 How to set the different addresses When 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not to damage any of the surrounding parts 1 Remove the front grille 6 screws 3 front grille fixtures 2 Remove the metal plate electrical ...

Page 11: ... breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and outdoor units are installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling heating function Refrigerant g...

Page 12: ... 1611 HT M16B117 The two dimensional bar code is a manufacturing code 3P457790 1 ...

Reviews: