background image

English

8

Refrigerant Piping Work

WARNING

• Do not apply mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R410A unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Incomplete flaring may result in refrigerant gas leakage.

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface facing downward, 

so that the filings do not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring has been done correctly.

2.

Refrigerant piping

CAUTION

• Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

• Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a torque wrench.

Caution on piping handling 

• Protect the open end of the pipe against dust and moisture.
• All pipe bends should be as gentle as possible. Use a pipe bender for bending. 

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following: 
• Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C))
Be sure to use insulation that is designed for use with HVAC Systems. 

• ACR Copper only.
• Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as 

below. 

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• Using finishing tape, bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other 

piping.

Piping size

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation thickness

Gas side

O.D. 1/2 inch

(12.7mm)

1-15/16 inch (50mm)

or more

0.039 inch (1.0mm)

(C1220T-O)

I.D. 9/16-5/8 inch

(14-16mm)

13/32 inch

(10mm) Min.

O.D. 5/8 inch

(15.9mm)

I.D. 5/8-13/16 inch

(16-20mm)

Liquid side

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm)

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 5/16-13/32 inch

(8-10mm)

A

A

Flaring

Set exactly at the position shown below.

Die

0-0.020 inch

(0-0.5mm)

Clutch-type

Flare tool for 

R410A

0.039-0.059 inch

(1.0-1.5mm)

Clutch-type

(Rigid-type)

0.059-0.079 inch

(1.5-2.0mm)

Wing-nut type

(Imperial-type)

Conventional flare tool

The flare’s inner surface must be 

flaw-free.
When flaring, do not over-tighten 

and crack.

The pipe end must be evenly flared 

in a perfect circle.

Make sure that the flare nut is fitted.

Check

Cut exactly at 

right angles.

 Remove burrs.

Do not apply refrigeration 

oil to the outer surface.

Flare nut

Apply refrigeration 

oil only to the inner 

surface of the flare.

Do not apply refrigeration 

oil to the flare nut to avoid 

tightening with excessive 

torque.

Apply oil

Torque wrench

Piping union

Flare nut

Spanner

Tighten

Piping size

O.D. 5/8 inch

(15.9mm)

Gas side

Liquid side

O.D. 1/4 inch

(6.4mm)

Flare nut tightening 

torque

45-5/8–55-5/8ft • lbf

(61.8-75.4N • m)

O.D. 1/2 inch

(12.7mm)

36-1/2–44-1/2ft • lbf

(49.5-60.3N • m)

10-1/2–12-3/4ft • lbf

(14.2-17.2N • m)

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt 

and water out.

Rain

Be sure to 

place a cap.

Gas pipe

Liquid pipe

Gas pipe 

insulation

Liquid pipe 

insulation

Finishing tape Drain hose

01_EN_3P572321-1A.fm  Page 8  Thursday, August 8, 2019  10:47 AM

Summary of Contents for FTX18UVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Fran ais Espa ol MODELS FTX18UVJU FTX24UVJU Installation manual Manuel d installation Manual de instalaci n...

Page 2: ...eak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transport...

Page 3: ...ented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can...

Page 4: ...is circulated throughout the room 8 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 9 no laundry equipment...

Page 5: ...ine Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Caulk pipe hole gap with putty Front panel The service lid is removable Opening method 1 Remov...

Page 6: ...ss the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open the front pan...

Page 7: ...onnections as they may cause overheating electric shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block...

Page 8: ...nsfer some water to the indoor heat exchanger by pouring water into the drain pan 3 Make sure that water flows out of the drain hose 4 If drain hose extension or embedded drain piping is required use...

Page 9: ...for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid ref...

Page 10: ...en 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not...

Page 11: ...e used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system wil...

Page 12: ...1908 HT M18B295A The two dimensional bar code is a manufacturing code 3P572321 1A...

Reviews: