English

6

3-2. Left-side, left-back, or left-bottom piping

1) Switch around the drain plug and drain hose. 

2) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

3) Shape the refrigerant pipes along the pipe path marking 

on the 

 mounting plate.

4) Pass the drain hose and refrigerant pipes through the 

wall hole, then position the indoor unit on the 

 mounting 

plate hooks, using the 

 markings at the top of the indoor 

unit as a guide.

5) Open the front panel, then open the service lid. (Refer to 

Service lid

” on page 4.)

6) Pass the inter-unit wire from the outdoor unit through the 

feed-through wall hole and then through the back of the 
indoor unit. Pull them through the front side. Bend the ends 
of tie wires upward for easier work in advance. 
(If the inter-unit wire ends are to be stripped first, bundle 
wire ends with adhesive tape.)

7) Connect the refrigerant pipes.

8) In case of pulling the drain hose through the back of the indoor 

unit, wrap the refrigerant pipes and drain hose together with 
insulation tape as shown in the figure.

9) Press the bottom frame of the indoor unit with both hands until it is 

firmly caught by the 

 mounting plate hooks. Make sure that the 

wires do not catch on the edge of the indoor unit.

3-3. Wall embedded piping 

Follow the instructions given under left-side, left-back, or 
left-bottom piping.

1) Insert the drain hose to a depth of 50mm or more so it 

will not be pulled out of the drain pipe.

4.

Wiring

Refer to the installation manual for the outdoor unit also.

WARNING

• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

3) Switch around the drain hose and drain plug.

1) Remove the fixing screw and 

pull out the drain hose.

How to switch around the drain plug and drain hose

Push the drain plug all the 

way in using a hexagonal 

wrench (3/16 inch (4mm)).

Hexagonal wrench 

(3/16 inch (4mm))

Drain plug

No gap

Do not apply lubricating oil 

(refrigerant oil) to the drain 

plug when inserting it.

The application of lubrication 

oil to the drain plug will 

deteriorate the plug to cause 

drain leakage from the plug.

Drain hose

     Remove fixing 

screw.

1

     Pull out 

drain hose.

2

Insert drain hose securely 

and fix in place with fixing 

screw.

Drain hose

Fixing screw

Insert a hexagonal 

wrench (3/16 inch (4mm)).

2) Pull out 

drain plug.

Remove pipe port cover here for 

left-bottom piping.

Remove pipe port 

cover here for 

left-side piping.

Left-bottom piping

Left-side piping
Left-back piping

A

Wrap insulation tape 

around the bent portion 

of refrigerant pipe. 

Overlap at least half the 

width of the insulation 

tape with each turn.

 A Mounting 

plate

Bind with 

adhesive 

vinyl tape.

Caulk this hole 

with putty or 

caulking material.

Drain 

hose

A

Refrigerant

pipes

Drain hose

Bottom frame

Mounting

plate

A

Secure the indoor unit to the     mounting plate with the

    indoor unit fixing screws M4 × 1/2” (M4 × 12mm)(2 points).

A

H

A

Inner wall

Vinyl chloride 

drain pipe (VP-30)

Drain hose

φ

1-3/16” (30mm) or more

1-15/16”

(50mm)

or more

Insert the drain hose 

to this depth so it will 

not be pulled out of 

the drain pipe.

Outer wall

01_EN_3P572321-1A.fm  Page 6  Thursday, August 8, 2019  10:47 AM

Summary of Contents for FTX18UVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Fran ais Espa ol MODELS FTX18UVJU FTX24UVJU Installation manual Manuel d installation Manual de instalaci n...

Page 2: ...eak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transport...

Page 3: ...ented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can...

Page 4: ...is circulated throughout the room 8 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 9 no laundry equipment...

Page 5: ...ine Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Caulk pipe hole gap with putty Front panel The service lid is removable Opening method 1 Remov...

Page 6: ...ss the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open the front pan...

Page 7: ...onnections as they may cause overheating electric shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block...

Page 8: ...nsfer some water to the indoor heat exchanger by pouring water into the drain pan 3 Make sure that water flows out of the drain hose 4 If drain hose extension or embedded drain piping is required use...

Page 9: ...for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid ref...

Page 10: ...en 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not...

Page 11: ...e used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system wil...

Page 12: ...1908 HT M18B295A The two dimensional bar code is a manufacturing code 3P572321 1A...

Reviews: