Indoor Unit Installation

1.

Installing the mounting plate

The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1)Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the drilling points 

on the wall.

2)Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions 

2.

Drilling a wall hole and installing wall embedded pipe

WARNING

For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole to 
prevent possible heat, electric shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material.

 (to prevent condensation caused by intrusion of air from outside or within the wall)

1) Drill a feed-through hole with a 

3-1/8 inch (80mm) diameter through the wall at 

a downward angle toward the outside. (to prevent water leakage)

2) Insert a wall embedded pipe into the hole.
3) Insert a wall hole cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk the pipe hole 

gap with putty.

3.

Installing the indoor unit

In the case of bending or curing refrigerant pipes, keep the following precautions in mind. Abnormal sound may be generated 
if improper work is conducted.
• Do not strongly press the refrigerant pipes onto the bottom frame.
• Do not strongly press the refrigerant pipes on the front grille, either.

3-1. Right-side, right-back, or right-bottom piping 

1) Attach the drain hose to the underside of the refrigerant 

pipes with adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with 

an insulation tape. 

3) Pass the drain hose and refrigerant pipes through the wall hole, then 

position the indoor unit on the 

 mounting plate hooks, using the 

 

markings at the top of the indoor unit as a guide. 

4) Open the front panel, then open the service lid. 

(Refer to 

“Service lid”

 on page 4.)

5) Pass the inter-unit wire from the outdoor unit through the feed-through wall hole and 

then through the back of the indoor unit. Pull them through the front side. Bend the 
ends of cable tie wires upward for easier work in advance. (If the inter-unit wire ends 
are to be stripped first, bundle wire ends with adhesive tape.) 

6) Press the bottom frame of the indoor unit with both hands until it is firmly caught by 

the 

 mounting plate hooks. Make sure that the wires do not catch on the edge of the 

indoor unit.

unit: inch (mm)

Use a tape 

measure 

as shown.

Position the 

end of the tape 

measure at 

.

Place the pipe port cover 

in this pocket.

Through-the-wall 

hole 

ϕ

3-1/8 (

ϕ

80)

Recommended mounting plate 

retention spots (9 spots in all)

(Bolt size : 3/8 (M10))

(Bolt size : 3/8 (M10))

Place a leveler on these tab.

Gas pipe end 

Liquid pipe end

4-11/16

(119)

41-5/16 (1050)

2-9/16

(65)

1-3/4 (45)

13-3/8  (340)

5-7/8

(149)

1-3/4 (45)

7-3/16 (182.5)

3-1/2

(89)

2-9/16

(65)

15-1/4 (388)

2-1/16 (53)

7-1/2 (190)

ϕ

3-1/8

(

ϕ

80)

ϕ

3-1/8

(

ϕ

80)

Drain hose 

position

5-1/4 (134)

Removed pipe 

port cover 

A Mounting 

plate

  The removed pipe port 

cover can be kept in the 

mounting plate pocket.

Inside

Outside

Caulking

(field supply)

Wall embedded pipe 

(field supply)

Even if a wall hole cover is not used, caulk both 

the outdoor and indoor sides with putty.

Wall hole cover

(field supply)

φ

3-1/8”

(80mm)

Right-

bottom 

piping

Right-side piping

Right-back piping

Bind refrigerant pipe and 

drain hose together with 

adhesive vinyl tape.

Remove pipe port 

cover here for 

right-side piping.

Remove pipe port 

cover here for 

right-bottom piping.

A

Mounting plate

A

Hang indoor 

unit’s hook 

here.

Mounting 

plate

A

A

01_EN_3P572321-1A.fm  Page 5  Thursday, August 8, 2019  10:47 AM

Summary of Contents for FTX18UVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Fran ais Espa ol MODELS FTX18UVJU FTX24UVJU Installation manual Manuel d installation Manual de instalaci n...

Page 2: ...eak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transport...

Page 3: ...ented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can...

Page 4: ...is circulated throughout the room 8 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 9 no laundry equipment...

Page 5: ...ine Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Caulk pipe hole gap with putty Front panel The service lid is removable Opening method 1 Remov...

Page 6: ...ss the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open the front pan...

Page 7: ...onnections as they may cause overheating electric shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block...

Page 8: ...nsfer some water to the indoor heat exchanger by pouring water into the drain pan 3 Make sure that water flows out of the drain hose 4 If drain hose extension or embedded drain piping is required use...

Page 9: ...for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid ref...

Page 10: ...en 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not...

Page 11: ...e used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system wil...

Page 12: ...1908 HT M18B295A The two dimensional bar code is a manufacturing code 3P572321 1A...

Reviews: