INSTALLATION MANUAL

DAIKIN ROOM AIR CONDITIONER

R410A Split Series

English

Français

Español

MODELS

FTX18UVJU
FTX24UVJU

Installation manual

Manuel d’installation

Manual de instalación

00_CV_3P572321-1A.fm  Page 1  Thursday, August 8, 2019  10:14 AM

Summary of Contents for FTX18UVJU

Page 1: ...INSTALLATION MANUAL DAIKIN ROOM AIR CONDITIONER R410A Split Series English Fran ais Espa ol MODELS FTX18UVJU FTX24UVJU Installation manual Manuel d installation Manual de instalaci n...

Page 2: ...eak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transport...

Page 3: ...ented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can...

Page 4: ...is circulated throughout the room 8 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 9 no laundry equipment...

Page 5: ...ine Do not connect commercially available drain hose directly to the indoor unit Water leakage may result Caulk pipe hole gap with putty Front panel The service lid is removable Opening method 1 Remov...

Page 6: ...ss the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the mounting plate hooks using the markings at the top of the indoor unit as a guide 4 Open the front pan...

Page 7: ...onnections as they may cause overheating electric shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block...

Page 8: ...nsfer some water to the indoor heat exchanger by pouring water into the drain pan 3 Make sure that water flows out of the drain hose 4 If drain hose extension or embedded drain piping is required use...

Page 9: ...for use with HVAC Systems ACR Copper only Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as below Use separate thermal insulation pipes for gas and liquid ref...

Page 10: ...en 2 indoor units are installed in one room the 2 wireless remote controllers can be set for different addresses Change the address setting of one of the 2 units When cutting the jumper be careful not...

Page 11: ...e used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system wil...

Page 12: ...1908 HT M18B295A The two dimensional bar code is a manufacturing code 3P572321 1A...