background image

2

English

 

•  Do not install unit in an area where flammable materials 

are present due to risk of explosion resulting in serious 
injury or death. 

•  Do not ground units to telephone wires or lightning rods 

because lightning strikes could cause a severe shock 
hazard resulting in severe injury or death, and to gas 
pipes because a gas leak could result in an explosion 
which could lead to severe injury or death.

WARNING 

•  Installation shall be left to the authorized dealer or another 

trained professional.  
Improper installation may cause water leakage, electrical 
shock, fire, or equipment damage.

•  Install the air conditioner according to the instructions 

given in this manual. 
Incomplete installation may cause water leakage, 
electrical shock, fire or equipment damage.

•  Be sure to use the supplied or exact specified installation 

parts. 
Use of other parts may cause the unit to come to fall, 
water leakage, electrical shock, fire or equipment damage.

•  Install the air conditioner on a solid base that is level and 

can support the weight of the unit. 
An inadequate base or incomplete installation may cause 
injury or equipment damage in the event the unit falls off 
the base or comes loose.

•  Electrical work shall be carried out in accordance with 

the installation manual and the national, state and local 
electrical wiring codes. 
Insufficient capacity or incomplete electrical work may 
cause electrical shock, fire or equipment damage.

•  Be sure to use a dedicated power circuit. Never use a 

power supply shared by another appliance.  
Follow all appropriate electrical codes.

•  For wiring, use a wire or cable long enough to cover the 

entire distance with no splices if possible.  
Do not use an extension cord. Do not put other loads on 
the power supply.  
Use only a separate dedicated power circuit.  
(Failure to do so may cause abnormal heat, electric shock, 
fire or equipment damage.)

•  Use the specified types of wires for electrical connections 

between the indoor and outdoor units.  
Follow all state and local electrical codes.  
Firmly clamp the inter-unit wire so their terminals receive 
no external stresses.  
Incomplete connections or clamping may cause terminal 
overheating, fire or equipment damage.

•  After connecting all wires be sure to shape the cables so 

that they do not put undue stress on the electrical covers, 
panels or terminals. 
Install covers over the wires. Incomplete cover installation 
may cause terminal overheating, electrical shock, fire or 
equipment damage.

•  When installing or relocating the system, be sure to keep 

the refrigerant circuit free from all substances other than 
the specified refrigerant (R410A), such as air. 
 (Any presence of air or other foreign substance in the 
refrigerant circuit causes an abnormal pressure rise which 
may result in rupture, resulting in injury.)

•  During pump down, stop the compressor before removing 

the refrigerant piping.  
If the compressor is still running and the stop valve is 
open during pump down, air will be sucked in when the 
refrigerant piping is removed, causing abnormally high 
pressure which could lead to equipment damage or and 
personal injury.

•  During installation, attach the refrigerant piping securely 

before running the compressor. 
If the refrigerant pipes are not attached and the stop valve 
is open during installation, air will be sucked in when the 
compressor is run, causing abnormally high pressure 
which could lead to equipment damage and personal 
injury.

•  Be sure to install a ground fault circuit interrupter.  

Failure to install a ground fault circuit interrupter may 
result in electrically shocks, or fire personal injury.

CAUTION 

•  Do not install the air conditioner where gas leakage would 

be exposed to open flames. 
If the gas leaks and builds up around the unit, it may catch 
fire.

•  Establish drain piping according to the instructions of this 

manual.  
Inadequate piping may cause water damage.

•  Tighten the flare nut according to the specified torque. A 

torque wrench should be used.  
If the flare nut is tightened too much, the flare nut may 
crack over time and cause refrigerant leakage.

•  Do not touch the heat exchanger fins.  

Improper handling may result in injury.

•  Be very careful about product transportation. 

Some products use PP bands for packaging. Do not 
use any PP bands for a means of transportation. It is 
dangerous.

•  Electrical work must be performed in accordance with the 

NEC/CEC by authorized personnel only.

English

01_EN_3P379970-1.indd   2

10/17/2014   12:57:21 PM

Summary of Contents for FTX09NMVJU

Page 1: ...t Series Installation manual Manuel dinstallation Manual de instalaci n MODELS FTX09NMVJU FTX12NMVJU FTX18NMVJU FTX24NMVJU FTXN09NMVJU FTXN12NMVJU FTXN18NMVJU FTXN24NMVJU FTK09NMVJU FTK12NMVJU FTK18NM...

Page 2: ...lation work check that the refrigerant gas does not leak Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas...

Page 3: ...ncomplete connections or clamping may cause terminal overheating fire or equipment damage After connecting all wires be sure to shape the cables so that they do not put undue stress on the electrical...

Page 4: ...he installation requirements specified in Indoor unit installation drawings on page 4 are met 2 both the air inlet and air outlet are unobstructed 3 the unit is not exposed to direct sunlight 4 the un...

Page 5: ...release the hooks If it is dif cult to release remove the front grille 1 3 16 30mm or more from ceiling Front panel 1 15 16 50mm or more from walls on both sides Air lters A A The 18 and 24 class mode...

Page 6: ...spots in all Place a leveler on these tabs 1 3 4 44 5 1 3 4 44 5 1 7 8 48 13 1 4 337 11 1 4 285 6 11 16 170 1 7 8 48 1 15 16 50 6 11 16 170 4 5 8 116 5 4 5 8 117 13 1 4 337 8 3 8 213 9 5 16 237 Drain...

Page 7: ...back or right bottom piping 1 Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape 2 Wrap the refrigerant pipes and drain hose together with J insulation tape Right...

Page 8: ...e refrigerant pipes along the pipe path marking on the A mounting plate 4 Pass the drain hose and refrigerant pipes through the wall hole then position the indoor unit on the A mounting plate hooks us...

Page 9: ...t mounting plate Conduit L1 L2 WARNING Do not use tapped wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical p...

Page 10: ...leakage 2 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent cracking of the flare nut as a result of deterioration over time To prevent gas leakage apply refrigera...

Page 11: ...1220T O I D 15 32 19 32 inch 12 15mm I D 9 16 5 8 inch 14 16mm I D 5 8 13 16 inch 16 20mm I D 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Minimum bend radius Piping thickness Thermal insulation size Th...

Page 12: ...odels have 3 screws 3 Install the air filter and then mount the front panel 3 How to set the different addresses When 2 indoor units are installed in one room the 2 wireless remote controllers can be...

Page 13: ...tically after about 30 minutes To stop the operation press Some of the functions cannot be used in the trial operation mode HEAT PUMP model COOLING ONLY model The air conditioner draws a small amount...

Page 14: ...installation v rifiez que le gaz r frig rant ne fuit pas Le gaz r frig rant peut produire un gaz toxique s il entre en contact avec une flamme comme partir d un ventilateur de chauffage une cuisini r...

Page 15: ...aucune contrainte externe Des connexions ou un serrage incomplets peuvent provoquer un chauffement des bornes un incendie ou un endommagement de l quipement Apr s avoir raccord tous les fils assurez v...

Page 16: ...s Sch mas d installation de l unit int rieure la page 4 sont remplies 2 l entr e d air et la sortie d air ne sont pas obstru es 3 l unit n est pas directement expos e la lumi re directe du soleil 4 l...

Page 17: ...de la grille avant pour lib rer les crochets S ils sont dif ciles lib rer retirez la grille avant 1 3 16 30mm ou plus du plafond Panneau avant 1 15 16 50mm ou plus des murs des deux c t s Filtres air...

Page 18: ...un v rin sur ces languettes 1 3 4 44 5 1 3 4 44 5 1 7 8 48 13 1 4 337 11 1 4 285 6 11 16 170 1 7 8 48 1 15 16 50 6 11 16 170 4 5 8 116 5 4 5 8 117 13 1 4 337 8 3 8 213 9 5 16 237 Position du tuyau d v...

Page 19: ...ixez le tuyau d vacuation la partie inf rieure des tuyaux de r frig rant avec du ruban vinyle adh sif 2 Enveloppez les tuyaux de r frig rant et le tuyau d vacuation avec du ruban isolant J Tuyauterie...

Page 20: ...rig rant le long du trac du tuyau sur la plaque de montage A 4 Faites passer le tuyau d vacuation et les tuyaux de r frig rant travers le trou dans le mur puis positionnez l unit int rieure sur les cr...

Page 21: ...L1 L2 AVERTISSEMENT N utilisez pas de c bles taraud s de c ble de rallonge ni de connexions en toile car ils peuvent provoquer une surchauffe une lectrocution ou un incendie N utilisez pas de pi ces...

Page 22: ...nt ATTENTION Utilisez l crou vas fix l unit principale Pour viter la fissuration de l crou vas suite une d t rioration au fil du temps Pour viter les fuites de gaz appliquez de l huile r frig rante un...

Page 23: ...15 32 19 32 inch 12 15mm Dia int 9 16 5 8 inch 14 16mm Dia int 5 8 13 16 inch 16 20mm Dia int 5 16 13 32 inch 8 10mm 13 32 inch 10mm Min Rayon de courbure minimum paisseur des tuyaux Taille de l isol...

Page 24: ...r puis montez le panneau avant 3 Comment d finir les diff rentes adresses Lorsque 2 unit s int rieures sont install es dans une seule pi ce les 2 t l commandes sans fil peuvent tre configur es pour de...

Page 25: ...tomatiquement apr s environ 30 minutes Pour arr ter le fonctionnement appuyez sur Certaines des fonctions ne peuvent pas tre utilis es dans le mode de fonctionnement d essai Mod le de POMPE CHALEUR Mo...

Page 26: ...aya fugas de gas refrigerante El gas refrigerante podr a producir gases t xicos al entrar en contacto con llamas como por ejemplo un termoventilador una estufa o un dispositivo de cocina La exposici n...

Page 27: ...externas Una conexi n o fijaci n incompleta puede causar el sobrecalentamiento del terminal incendios o da os al equipo Despu s de conectar todos los cables aseg rese de que se encuentren de modo que...

Page 28: ...s en Esquemas de instalaci n de la unidad interior de la p gina 4 2 tanto la entrada de aire como la salida del aire no est n obstruidas 3 la unidad no est expuesta a la luz directa del sol 4 la unida...

Page 29: ...hos Si resulta dif cil liberar los ganchos extraiga la rejilla delantera 1 3 16 30mm o m s del techo Panel frontal 1 15 16 50mm o m s de las paredes en ambos lados Filtros de aire A A Los modelos de c...

Page 30: ...nivelador en estas leng etas 1 3 4 44 5 1 3 4 44 5 1 7 8 48 13 1 4 337 11 1 4 285 6 11 16 170 1 7 8 48 1 15 16 50 6 11 16 170 4 5 8 116 5 4 5 8 117 13 1 4 337 8 3 8 213 9 5 16 237 Posici n de la mangu...

Page 31: ...renaje en la parte inferior de las tuber as refrigerantes con cinta de vinilo adhesiva 2 Envuelva las tuber as refrigerantes y la manguera de drenaje conjuntamente con cinta aislante J Tuber a inferio...

Page 32: ...ayectoria de la tuber a en la placa de montaje A 4 Pase la manguera de drenaje y las tuber as refrigerantes por el orificio de la pared a continuaci n coloque la unidad interior sobre los ganchos de l...

Page 33: ...L2 ADVERTENCIA No use cables encintados cables de extensi n ni conexiones de estrella ya que podr an causar calentamientos descargas el ctricas o incendios No use partes el ctricas compradas localmen...

Page 34: ...efrigerante PRECAUCI N Use la tuerca abocinada fijada a la unidad principal Con ello evitar el agrietamiento de la tuerca abocinada como resultado de su deterioro por el paso del tiempo Para evitar fu...

Page 35: ...ch 0 8mm C1220T O D I 15 32 19 32 inch 12 15mm D I 9 16 5 8 inch 14 16mm D I 5 8 13 16 inch 16 20mm D I 5 16 13 32 inch 8 10mm 13 32 inch 10mm m n Radio de curvatura m nimo Espesor de la tuber a Tama...

Page 36: ...o de aire y a continuaci n monte el panel frontal 3 C mo ajustar distintas direcciones Cuando instale 2 unidades interiores en una habitaci n los 2 controles remotos inal mbricos pueden ajustarse a di...

Page 37: ...unciones no pueden utilizarse en el modo de ope raci n de ensayo Modelo BOMBA CALEFACTORA Modelo SOLO REFRIGERACI N El aire acondicionado consume una peque a cantidad de energ a en el modo de estado d...

Page 38: ...13 Espa ol MEMO...

Page 39: ...Two dimensional bar code is a manufacturing code 3P379970 1 M14B059 1410 HT...

Reviews: