background image

1

English

Safety Precautions

• The precautions described herein are classified as WARNING and CAUTION. They both contain important information 

regarding safety. Be sure to observe all precautions without fail.

• Meaning of WARNING and CAUTION notices

WARNING ..........Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION ...........Failure to observe these instructions properly may result in property damage or personal injury, 

which may be serious depending on the circumstances.

• The safety marks shown in this manual have the following meanings:

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate 

the air conditioner and take care of it with the aid of the operation manual.

• The English text is the original instruction. Other languages are translations of the original instructions.

Be sure to follow the instructions. 

Be sure to establish an earth connection. 

Never attempt. 

WARNING

• Ask your dealer or qualified personnel to carry out installation work.

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire. 

• Install the air conditioner in accordance with the instructions in this installation manual.

Improper installation may result in water leakage, electric shocks or fire. 

• Be sure to use only the specified accessories and parts for installation work.

Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.

A foundation of insufficient strength may result in the equipment falling and causing injury. 

• Electrical work must be performed in accordance with relevant local and national regulations and with instructions 

in this installation manual. Be sure to use a dedicated power supply circuit only.

Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

• Use a cable of suitable length.

Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire. 

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections or wires.

Improper connections or securing of wires may result in abnormal heat build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires 

so that the control box lid can be securely fastened.

Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, 
stove or cooker.

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, 

and use only the specified refrigerant (R22).

The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage and even 
injury.

• During installation, attach the refrigerant piping securely before running the compressor.

If the compressor is not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal pressure in the 
refrigeration cycle, which may result in equipment damage and even injury. 

• During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric shocks or fire. 

• Do not touch any electronic component or terminal when the machine is running, stopping or has been powered off 

for less than 30 minutes to prevent the risk of electric shock!

Summary of Contents for FTV25AV1

Page 1: ...R22 Split Series MODEL FTV25AV1 FTV35AV1 FTV50AV1 FTV60AV1 RV25AV1 RV35AV1 RV50AV1 RV60AV1 OWNER S MANUAL...

Page 2: ......

Page 3: ...concentration Possible chemical symbols are Pb lead 0 004 Do not try to dismantle the system yourself the dismantling of the product treatment of the refrigerant of oil and of other parts must be done...

Page 4: ...etection 15 Check after installation 16 Test and operation Test operation 16 Attachment Configuration of connection pipe 17 Pipe expanding method 18 Screen Operation Guide Buttons on remote controller...

Page 5: ...rheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of...

Page 6: ...der to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep...

Page 7: ...MER LIGHT X FAN MODE SAVE FAN SWING ON OFF TURBO air inlet panel filter aux button horizontal louver air outlet display remote controller receiver window power indicator Timer Indoor Unit air inlet ha...

Page 8: ...0cm At least 30cm At least 300cm At least 200cm Space to the obstruction Space to the obstruction Space to the obstruction Space to the ceiling Space to the floor Space to the obstruction Space to the...

Page 9: ...obstruction near air inlet and air outlet 2 Select a location where the condensation water can be dispersed easily and won t affect other people 3 Select a location which is convenient to connect the...

Page 10: ...milarly qualified persons in order to avoid hazard 8 The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube 9 The appliance shall be instal...

Page 11: ...he frame If the plastic expansion particle is loose please drill another fixing hole nearby Step three open piping hole 1 Choose the position of piping hole according to the direction of outlet pipe T...

Page 12: ...on nut with torque wrench Piping hole Model 55 Cooling capacity 6000W 70 Cooling capacity 6000W 5 10 55 70 Note Pay attention to dust prevention and take relevant safety measures when opening the hole...

Page 13: ...or unit 1 Open the panel remove the screw on the wiring cover and then take down the cover Hex nut diameter Tightening torque N m 6 15 20 9 52 30 40 12 40 55 16 60 65 19 70 75 torque wrench indoor pip...

Page 14: ...ote All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire is insufficient see table below please contact the supplier for a new one Avo...

Page 15: ...a certain length of drain hose and power cord for installation when binding them When binding to a certain degree separate the indoor power and then separate the drain hose indoor unit indoor and out...

Page 16: ...or in order to install drain joint For the unit with cooling capacity of 2300W 5000W 6 expansion screws are needed for the unit with cooling capacity of 6000W 8000W 8 expansion screws are needed for t...

Page 17: ...nd 4 Tighten the union nut with torque wrench by referring to the sheet below Hex nut diameter Tightening torque N m 6 15 20 9 52 30 40 12 40 55 16 60 65 19 70 75 yellow green pipe joint union nut 1 R...

Page 18: ...in order to prevent rain from getting into the room Note After tightening the screw pull the power cord slightly to check if it is firm U shaped curve drain hose wall Note The through wall height of d...

Page 19: ...ecreases there may be leakage 5 Remove the piezometer open the valve core of liquid valve and gas valve completely with inner hexagon spanner 6 Tighten the screw caps of valves and refrigerant chargin...

Page 20: ...pacity Is heat insulation of pipeline sufficient It may cause condensation and water dripping Is water drained well It may cause condensation and water dripping Is the voltage of power supply accordin...

Page 21: ...connection pipe is above 10m add refrigerant according to the extra length of liquid pipe The additional refrigerant charging amount per meter is different according to the diameter of liquid pipe See...

Page 22: ...e the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe pipe cutter pipe leaning uneven burr pipe shaper downwards union pipe pipe E Expand the port Expand th...

Page 23: ...reen ON OFF button MODE button button FAN button SWING button SAVE button X FAN button TIMER button TURBO button SLEEP button LIGHT button Child Lock Dry mode Auto mode Cool mode Heat mode Fan mode X...

Page 24: ...ient temperature The set temperature can t be adjusted and also can t be displayed Press the FAN button to adjust fan speed Press the SWING button to adjust swing angle After selecting the cool mode t...

Page 25: ...R OFF or Clock setting you can press the or button to adjust time Refer to TIMER button for details Press this button to select the fan speed in sequence auto AUTO low speed medium speed high speed No...

Page 26: ...der the X FAN mode press X FAN button to turn off the X FAN function The indoor fan will stop operating immediately At ON status press this button once to set TIMER OFF The character of HOUR and OFF w...

Page 27: ...displayed Press this button to turn off the light on the display of the indoor unit Press this button again to turn on the light on the display of the indoor unit Introduction to functions of combinat...

Page 28: ...7 AAA 1 5V dry batteries and make sure the position of polar and polar are correct 3 Reinstall the cover of battery box signal sender battery reinstall remove Cover of battery box During operation po...

Page 29: ...he air conditioner The operation in details are as below As shown in the fig Open panel press aux button to turn on or off the air conditioner When the air conditioner is turned on it will operate und...

Page 30: ...t it in a shady and cool place to dry 3 Remove filter Remove the filter as indicated in the fig 2 Install filter Install the filter and then close the panel cover tightly 4 The filter should be cleane...

Page 31: ...hether drainage pipe is damaged Checking before active season 1 Disconnect power supply 2 Clean filter and indoor unit s panel 3 Check whether mounting bracket for outdoor unit is damaged or corroded...

Page 32: ...e remote controller at the receiving window on indoor unit Is sensitivity of remote controller low fuzzy display and no display Check the batteries If the power of batteries is too low please replace...

Page 33: ...ndoor unit s air outlet Indoor temperature and humidity is high Because indoor air is cooled rapidly After a while indoor temperature and humidity will decrease and mist will disappear Set temperature...

Page 34: ...rigerant flowing inside the unit which is a normal phenomenon Cracking noise Air conditioner is turned on or turned off just now This is the sound of friction caused by expansion and or contraction of...

Page 35: ...tch Tighten the terminal screws securely We recommend a flathead screw driver be used to tighten the screws 3 For connecting outdoor unit to indoor unit use standardized supply cable H05RN 1 2 3 1 2 3...

Page 36: ...the jumper U D Up Down GN Green Outdoor Unit AP Printed Circuit Board TEM Sensor Temperature Sensor RT Thermistor OVC COMP Compressor Overload Protector EKV Electronic expansion valve coil CN Connect...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...66129915142 Copyright 2013 Daikin...

Reviews: