Allowable Piping Length and Maximum No. of Bends
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
REFRIGERANT PIPING
Indoor unit
Outdoor Unit
L
E
Remark:
The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
*
Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Model
Indoor
FT(Y)NV20
FT(Y)NV25
FT(Y)NV30
FT(Y)S20
FT(Y)S25
Outdoor
R(Y)NV20
R(Y)NV25
R(Y)NV30
R(Y)S20
R(Y)S25
Min. allowable length, m
3
3
3
Max. allowable length, m (L)
30
45
30
Max. allowable elevation, m (E)
15
25
15
Liquid pipe size, mm/(in)
6.35
(1/4")
6.35
(1/4")
9.53
(3/8")
6.35
(1/4")
6.35
(1/4")
Gas pipe size, mm/(in)
12.7
(1/2")
15.88
(5/8")
15.88
(5/8")
12.7
(1/2")
15.88
(5/8")
Bending must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe where possible.
Equivalent length for various fitting (meter)
Pipe Size
L joint
Trap bend
3/8" (OD9.52mm)
0.18
1.3
1/2" (OD12.7mm)
0.20
1.5
5/8" (OD15.9mm)
0.25
2
3/4" (OD19.1mm)
0.35
2.4
7/8" (OD22.2mm)
0.40
3
1" (OD25.4mm)
0.45
3.4
1 1/8" (OD28.6mm)
0.50
3.7
1 3/8" (OD34.9mm)
0.60
4.4
Notes:
1. Equivalent piping length is obtained with actual length of gas piping.
2. 90° bend of piping is equivalent to L joint.
1-IM-5WMJ(R)-0714(2)DAIKIN(SASO)10 10