INSTALLATION
MANUAL

MODELS
FTD20JEV1K   RD20JEV1K
FTD25JEV1K    RD25JEV1K

R22 SPLIT SERIES

English

Installation Manual

R22 Split Series

IM-WMJ-1111(0)-DAIKIN

Part No.: R08019033301

1-CVR EN-IM WMJ-1111(0)Daikin.in1   1

11/29/11   2:16:02 PM

Summary of Contents for FTD20JEV1K

Page 1: ...INSTALLATION MANUAL MODELS FTD20JEV1K RD20JEV1K FTD25JEV1K RD25JEV1K R22 SPLIT SERIES English Installation Manual R22 Split Series IM WMJ 1111 0 DAIKIN Part No R08019033301...

Page 2: ......

Page 3: ...E TERMINAL BLOCK WITH EARTH TERMINAL All dimensions are in mm Original Instruction OUTLINE AND DIMENSIONS D B G H J L M A K F I G F E Through the wall hole 65mm Drain hose position Liquid pipe end Gas...

Page 4: ...mm Outdoor Unit Dimension Model A B C D E F G H I J K L M N O RD20JEV1K 855 628 328 520 181 44 93 149 101 113 603 126 164 17 34 RD25JEV1K 855 730 328 520 182 44 93 149 101 113 603 126 164 17 34 Dimen...

Page 5: ...useinroomwheremineraloil oilvapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep flour away...

Page 6: ...the smooth air flow Please follow the installation clearances shown in the figure Select the coolest possible place where intake air temperature is not greater than the outside air temperature please...

Page 7: ...to the required position in order to align it with the holes For the side and bottom hold the bottom of the piping and then position it to the required direction see figure The condensation drain hose...

Page 8: ...indoor unit with the upper edge of the installation plate Ensure that the hooks are properly seated on the installation plate by moving it to the left and right How To Attach The Indoor Unit Hook the...

Page 9: ...iquid Pipe Size mm in 6 35 1 4 9 52 3 8 L E Remark The refrigerant pre charged in the outdoor unit is for piping length up to 7 5m Be sure to add the proper amount of additional refrigerant Failure to...

Page 10: ...cause gas leak Insert the flare nuts mounted on the connection parts of both the indoor unit and outdoor unit into the copper pipes The exact length of pipe protruding from the top surface of the swa...

Page 11: ...d All wires must not touch the refrigerant piping compressor or any moving parts of the fan motor The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps T...

Page 12: ...vacuum pump Evacuate for approximately 30 minutes The evacuation time varies with different vacuum pump capacity Confirm that the charging gauge needle has moved towards 760mmHg Caution If the gauge...

Page 13: ...Indicator Lights for Cooling Unit IR Receiver Cooling Unit The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions The LED indicator lights ar...

Page 14: ...e Room air sensor contact Loose Short Call your dealer Blink E1 3 times Outdoor coil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compressor o...

Page 15: ...occur on the louver thus resulting in drippings Frost Prevention When the air lter is dirty the evaporating temperature will decrease and eventually cause frosting If the evaporating temperature reach...

Page 16: ...e old Bio Filter as nonflammable garbage after use Operation with dirty filters 1 cannot deodorize the air 3 results in poor heating or cooling 2 cannot clean the air 4 may cause odour To order Bio Fi...

Page 17: ...eft and pull it to the front side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with the grooves and push them all the way in Gently close the front...

Page 18: ...been set incorrectly If the fault persist after all these verifications please contact the air conditioner unit installer The air flow is too low 3 The air filter is dirty The doors or windows are ope...

Page 19: ......

Page 20: ...fication and design contain herein at any time without prior notification Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selangor Darul Ehsan Malays...