background image

7

English

Model

10m/32.8ft

12m/39.4ft

15m/49.2ft

FT20FV1M / FT25FV1M

35

65

-

FT28FV1M/FT35FV1M

FT50FV1M

35

65

-

FT60FV1M9

90

165

280

Additional Charge

The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.62m (25ft), then additional charge after vacuuming is
not necessary. If the piping length is more than 7.62m (25ft), then use the additional charge valve as indicated in the table.

Charge Operation

This operation must be done by using a gas cylinder and a precise weigh-
ing machine. The additional charge is topped-up into the outdoor unit
using the suction valve via the service port.
• Remove the service port cap.
• Connect the low pressure side of the charging gauge to the suction

service port center of the cylinder tank and close the high pressure
side of the gauge. Purge the air from the service hose.

• Start the air conditioner unit.
• Open the gas cylinder and low pressure charging valve.
• When the required refrigerant quantity is pumped into the unit, close

the low pressure side and the gas cylinder valve.

• Disconnect the service hose from service port. Put back the service

port cap.

Additional charge in gram (For R22 models)

Purging The Piping And The Indoor Unit

Except for the outdoor unit which is pre-charged with refrigerant, the indoor
unit and the refrigerant connection pipes must be air-purged because the air
containing moisture that remains in the refrigerant cycle may cause malfunc-
tion of the compressor.
• Remove the caps from the valve and the service port.
• Connect the center of the charging gauge to the vacuum pump.
• Connect the charging gauge to the service port of the 3-way valve.
• Start the vacuum pump. Evacuate for approximately 30 minutes. The

evacuation time varies with different vacuum pump capacity. Confirm that
the charging gauge needle has moved towards -760mmHg.

Caution:

• If the gauge needle does not move to -760mmHg, be sure to check for gas

leaks (using the refrigerant detector) at flare type connection of the indoor
and outdoor unit and repair the leak before proceeding to the next step.

• Close the valve of the charging gauge and stop the vacuum pump.
• On the outdoor unit, open the suction valve (3 way) and liquid valve (2 way)

(in anti- clockwise direction) with 4mm key for hexagon sacked screw.

Refrigerant Piping

Service Port

Outdoor Unit 3 Ways Valve

Flare Nut

Allen Key

Suction

valve

Discharge

 Valve

Indoor Unit

Outdoor Unit

Liquid side

Gas side

Vacuum
pump

Open

Close

Close

Close

Hi

Low

Liquid Side

Indoor Unit

Outdoor Unit

Gas Side

Vacuum

Pump

Open

Close

Hi

VACUUMING AND CHARGING

Open

Open

Suction

Valve

Discharge Valve

Indoor Unit

Outdoor Unit

Liquid side

Gas side

Check

Valve

Close

Hi

Low

Indoor Unit

Liquid Side

Outdoor Unit

Gas Side

Check

Valve

Low

Close

Hi

Summary of Contents for FT20FV1M

Page 1: ...14 WALL MOUNTED SPLIT TYPE AIR CONDITIONER WALL MOUNTED INSTALLATION MANUAL Part No R08019028786 IM WMG 0906 DAIKIN...

Page 2: ......

Page 3: ...5 2 FT28FV1M FT35FV1M 899 260 198 590 246 185 124 8 56 50 419 495 50 128 132 35 4 10 2 7 8 23 2 9 7 7 3 4 9 0 3 2 2 2 0 16 5 19 5 2 0 5 1 5 2 Dimension A B C D E FT50FV1M FT60FV1M9 1060 310 220 912 29...

Page 4: ...15 18 4 3 0 5 0 7 Dimension D E F R20FV1M R25FV1M 418 177 35 16 4 6 9 1 3 R35FV1M 485 175 36 19 1 6 8 1 4 3 0 1 Outdoor Unit Dimension A B C D E F G H I J K L M N O R50FV1M 855 628 328 513 182 44 93...

Page 5: ...esult of the excessive heat Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively IMPORTANT DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A L...

Page 6: ...Hose Fix With Vinyl Tape Mount The Unit Onto The Installation Plate Hook the indoor unit onto the upper portion of the installation plate Engage the two hooks at the rear top of the indoor unit with t...

Page 7: ...the copper tubings Cut the connection pipe with a pipe cutter Remove burrs from cut edges of the pipes with remover Hold the end of the pipe downwards to prevent metal chips from entering the pipe In...

Page 8: ...and selected to comply with the local national codes of regulations This is also subject to the type of installation and conductors used Cooling Unit Power From Indoor FT20 25 28 35FV1M COMP N2 COMP N...

Page 9: ...oor unit and the refrigerant connection pipes must be air purged because the air containing moisture that remains in the refrigerant cycle may cause malfunc tion of the compressor Remove the caps from...

Page 10: ...ndicator Lights for Cooling Unit Heat Pump Unit LED Indicator Lights IR Receiver LED Indicator Lights Normal Operation And Fault Conditions For Cooling Normal Operation Fault Indication Action Cool mo...

Page 11: ...ntal Air Flow Control For more effective air circulation you can manually adjust the air discharge grille to the left or right During cool mode operation and dry mode operation do not direct the air d...

Page 12: ...ile substances or chemicals to clean the indoor unit Period At least once every 2 weeks More frequently if necessary At least once every 2 weeks More frequently if necessary Service Parts Indoor air f...

Page 13: ...3 Flip open the air discharge housing 4 Clean the blower 5 Close the air discharge housing and tighten it with screw When The Unit Is Not To Be Used For An Extended Long Period Of Time Remove the powe...

Page 14: ...he doors or windows are open The air suction and discharge are clogged The regulated temperature is not high enough Odours may be caused by cigarettes smoke particles perfume etc which might have adhe...

Page 15: ......

Page 16: ...ame in any languages the ENGLISH version of this manual shall prevail The manufacturer reserves right to revise any of the specification and design contain herein at any time without prior notificatio...

Reviews: