6

N1

N2

COMP

L

L

N1

L1

COMP

N

All wires must be firmly connected.

All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.

The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.

The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.

Cooling Unit (Power From Outdoor) FT50FV1M/
FT60FV1M9

!

There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended in
the fixed installation circuit.

Power Supply Cable

Outdoor Unit

Terminal Block

Indoor Unit

Terminal Block

Outdoor coil sensor

connection wire (8m long)

attached in the indoor unit

ELECTRICAL WIRING CONNECTION

Cooling Unit
IMPORTANT:

* The figures shown in the table are for information purpose only. They should be checked and selected to

comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.

Cooling Unit (Power From Indoor) FT20/25/28/35FV1M

COMP

N2

COMP

N

N1

L

Outdoor Unit

Terminal Block

Indoor Unit

Terminal Block

There must be a double pole switch
with a minimum 3mm contact gap and
fuse/circuit breaker as recommended
in the fixed installation circuit.

!

Power Supply Cable

FT20FV1M

FT50FV1M

FT25FV1M

FT60FV1M9

Model

FT28FV1M
FT35FV1M

Voltage range

220V-240V / 1Ph / 50Hz + 

!

Power supply cable size*

mm

2

1.5

2.5

Number of wire

3

3

Interconnection cable size*

mm

2

2.0

2.0

Number of wire

3

3

Recommended fuse

A

15

20

Piping Connection To The Units

Align the center of the piping and tighten the flare nut suffi-
ciently with fingers.

Finally, tighten the flare nut with the torque wrench until the
wrench clicks.

Indoor Piping

Flare Nut

Flared Tube

Flare Joint

Pipe Size mm / (in)

Torque Nm / (ft - lb)

6.35 (1/4)

18 (13.3)

9.53 (3/8)

42 (31.0)

12.7 (1/2)

55 (40.6)

15.88 (5/8)

65 (48.0)

19.05 (3/4)

78 (57.6)

Spanar

Torque Wrench

Summary of Contents for FT20FV1M

Page 1: ...14 WALL MOUNTED SPLIT TYPE AIR CONDITIONER WALL MOUNTED INSTALLATION MANUAL Part No R08019028786 IM WMG 0906 DAIKIN...

Page 2: ......

Page 3: ...5 2 FT28FV1M FT35FV1M 899 260 198 590 246 185 124 8 56 50 419 495 50 128 132 35 4 10 2 7 8 23 2 9 7 7 3 4 9 0 3 2 2 2 0 16 5 19 5 2 0 5 1 5 2 Dimension A B C D E FT50FV1M FT60FV1M9 1060 310 220 912 29...

Page 4: ...15 18 4 3 0 5 0 7 Dimension D E F R20FV1M R25FV1M 418 177 35 16 4 6 9 1 3 R35FV1M 485 175 36 19 1 6 8 1 4 3 0 1 Outdoor Unit Dimension A B C D E F G H I J K L M N O R50FV1M 855 628 328 513 182 44 93...

Page 5: ...esult of the excessive heat Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively IMPORTANT DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A L...

Page 6: ...Hose Fix With Vinyl Tape Mount The Unit Onto The Installation Plate Hook the indoor unit onto the upper portion of the installation plate Engage the two hooks at the rear top of the indoor unit with t...

Page 7: ...the copper tubings Cut the connection pipe with a pipe cutter Remove burrs from cut edges of the pipes with remover Hold the end of the pipe downwards to prevent metal chips from entering the pipe In...

Page 8: ...and selected to comply with the local national codes of regulations This is also subject to the type of installation and conductors used Cooling Unit Power From Indoor FT20 25 28 35FV1M COMP N2 COMP N...

Page 9: ...oor unit and the refrigerant connection pipes must be air purged because the air containing moisture that remains in the refrigerant cycle may cause malfunc tion of the compressor Remove the caps from...

Page 10: ...ndicator Lights for Cooling Unit Heat Pump Unit LED Indicator Lights IR Receiver LED Indicator Lights Normal Operation And Fault Conditions For Cooling Normal Operation Fault Indication Action Cool mo...

Page 11: ...ntal Air Flow Control For more effective air circulation you can manually adjust the air discharge grille to the left or right During cool mode operation and dry mode operation do not direct the air d...

Page 12: ...ile substances or chemicals to clean the indoor unit Period At least once every 2 weeks More frequently if necessary At least once every 2 weeks More frequently if necessary Service Parts Indoor air f...

Page 13: ...3 Flip open the air discharge housing 4 Clean the blower 5 Close the air discharge housing and tighten it with screw When The Unit Is Not To Be Used For An Extended Long Period Of Time Remove the powe...

Page 14: ...he doors or windows are open The air suction and discharge are clogged The regulated temperature is not high enough Odours may be caused by cigarettes smoke particles perfume etc which might have adhe...

Page 15: ......

Page 16: ...ame in any languages the ENGLISH version of this manual shall prevail The manufacturer reserves right to revise any of the specification and design contain herein at any time without prior notificatio...

Reviews: