![Daikin FLXS-BAVMB Service Manual Download Page 32](http://html.mh-extra.com/html/daikin/flxs-bavmb/flxs-bavmb_service-manual_502275032.webp)
Outdoor Unit
SiBE05-722_B
21
Printed Circuit Board Connector Wiring Diagram
2.3
RK(X)S25/35G2V1B9, RXS25/35J2V1B
Connectors and
Other Parts
PCB (1): Filter PCB
PCB (2): Main PCB
PCB (3): Forced Operation Button PCB
1) S11
Connector for main PCB
2) AC1, AC2, S
Connector for terminal board
3) E1, E2
Terminal for earth
4) HL2, HN2
Connector for main PCB
5) HR1
Connector for reactor
6) FU1
Fuse (3.15 A, 250 V)
7) FU3
Fuse (20 A, 250 V)
8) V2, V3
Varistor
1) S10
Connector for filter PCB
2) S20
Connector for electronic expansion valve coil
3) S40
Connector for overload protector
4) S50
Connector for magnetic relay
5) S70
Connector for fan motor
6) S80
Connector for four way valve coil
7) S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
8) S100
Connector for forced operation button PCB
9) HL3, HN3
Connector for filter PCB
10)HR2
Connector for reactor
11)U, V, W
Connector for compressor
12)FU2
Fuse (3.15 A, 250 V)
13)LED A
LED for service monitor (green)
14)V1
Varistor
15)J4
Jumper for facility setting
∗
Refer to page 217 for detail.
16)J5
Jumper for improvement of defrost performance
∗
Refer to page 218 for detail.
1) S110
Connector for main PCB
2) SW1
Forced operation ON/OFF button