SiBE05-722_B
Troubleshooting
Service Diagnosis
94
Troubleshooting
RK(X)S25/35G2V1B, RK(X)S25/35G2V1B9, RXS25/35J2V1B models
Check No.07
Refer to P.107
Check No.09
Refer to P.108
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above
C
˚C and stops when it
drops below
B
˚C.
(R13536)
YES
NO
Slightly dirty
NG
Too dirty
OK
NO
YES
Turn off the power and turn it on
again.
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
Radiation fin dirty?
Above
A
˚C?
Check No. 09
Check the outdoor fan or
related.
Error again or outdoor
fan activated?
Replace the outdoor unit
PCB.
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the fan motor.
Correct the connectors and
fan motor lead wire.
Replace the outdoor unit
PCB.
A
(°C)
B
(°C)
C
(°C)
RK(X)S25/35G2V1B
80
70
80
RK(X)S25/35G2V1B9
RXS25/35J2V1B
98
75
83