background image

4

 • Check the pipe connector for gas leaks

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line
(supplied with the unit)

4

Insulation for fitting of gas line
(supplied with the unit)

5

Clamps (use 2 clamps
per insulation)

DRAIN PIPING WORK

Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.

1

Hanging bar

1. Install the drain pipes.

Keep piping as short as possible and slope it downwards
so that air may not remain trapped inside the pipe.

Keep pipe size equal to or greater than that of the
connecting pipe (Vinyl pipe of 25mm nominal diameter and
32mm outer diameter).

Use the supplied drain hose and metal clamp. Tighten the
clamp firmly.

1

Metal clamp

2

Drain hose

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit
the hose with drain raising piping (field supply).

HOW TO PERFORM PIPING (see figure 8)

1

Ceiling slab

2

Hanging bar

3

Adjustable range

4

Drain hose (supplied with the unit)

5

Metal clamp (supplied with the unit)

6

Drain raising pipe (field supply)

1 Connect the drain hose to the drain raising pipes, and insulate

them.

2 Connect the drain hose to the drain pipe on the indoor unit,

and tighten it with the metal clamp.

Installation

A

Rear suction installation

275

When canvas duct is installed

350-530

When air inlet panel is directly installed

275

To ensure a downward slope of 1:100, install hanging bars
every 1 to 1.5m.

If unifying multiple drain pipes, install the pipes as shown
in figure 9.

1

Multiple drain piping

2. After piping work is finished, check if drainage flows

smoothly.

Open the water inlet lid, add approximately 1l of water
gradually and check the drainage flow (see figure 10).

1

Water inlet

2

Portable pump

3

Water inlet lid

4

Bucket (adding water from water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

NOTE 

The drain outlet is only used to discharge water if the drain pump
is not used or before maintenance. Gently put in and out the
drain plug. Excessive force may deform the drain socket of the
drain pan.

WHEN ELECTRIC WIRING WORK IS FINISHED

Check drainage flow during COOL running, explained in chapter
"TEST OPERATION".

WHEN ELECTRIC WIRING WORK IS NOT FINISHED

Remove the switch box cover and connect the single-phase
power supply and the remote controller to the terminals.
(Refer to chapter "ELECTRIC WIRING WORK" for switch box
attachment/detachment) (Refer to figure 11a and 11b)

1

Switch box cover

2

Power supply wiring port

3

Transmission wiring port

4

Wiring diagram

5

Switch box

6

Plastic clamp

7

Remote controller wiring

8

Terminal board for unit transmission wiring

9

Power supply wiring

10

Emergency switch

11

Power supply terminal board

12

Earth screw

Remove the switch box cover and change the emergency
switch on the PC board of the indoor unit from "NORMAL" to
"EMERGENCY". Be sure to change the switch to
"EMERGENCY" before turning on the power.

Connect the single-phase power supply (50Hz; 230V) to
connections 1 and 3 (see figure below) on the power supply
terminal board and confirm drain operation.

Be aware that the fan will turn during the operation.

After confirming drainage, turn off the power and be sure to
change the emergency switch back to "NORMAL".

ELECTRIC WIRING WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the switch box cover
to wire the outdoor unit, indoor units and the remote
controller. For details on hooking up the remote controller,
refer to the "Installation manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

2

1

1

1-1.5m

1

2

3

5

3

1

2

4

Summary of Contents for FHYB100FK7V1

Page 1: ...Split System air conditioners INSTALLATION MANUAL FHYB35Fk7V1 FHYB45Fk7V1 FHYB60Fk7V1 FHYB71Fk7V1 FHYB100Fk7V1 FHYB125Fk7V1 FHB35Fk7V1 FHB45Fk7V1 FHB60Fk7V1 ...

Page 2: ...standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning är utförd i överensstämmelse med och följer följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgi...

Page 3: ...0 1 4 3 4 2 800 630 B A 145 2 5 6 7 4 3 2 3 1 4 680 85 1 3 2 4 6 5 50 200 45 680 1 5 2 3 7 4 680 65 5 1 2 3 2 4 460 180 A 160 160 300 425 4 2 2 3 1 460 180 350 A 1 100mm 3 2 1 6 5 4 1 3 2 2 1 3 1 3 2 4 5 2 1 2 3 1 1 5m 0 625mm 2 6 1 5 4 A 3 ...

Page 4: ...12 11a 11b 11c 3 5 1 2 4 2 2 1 1 2 S M S S M 1 2 3 5 4 1 3 2 9 11 12 6 7 9 6 12 8 10 5 EMERG NORM 15 14 17 18 13 16 1 2 3 4 5 6 1 2 3 4 5 6 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 ...

Page 5: ...of the outdoor unit for items not described in this manual Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machi...

Page 6: ...nce for maintenance and service can be ensured Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the outdoor unit Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical appliances Noise may be...

Page 7: ...utside with refrigerating machine oil and initially tighten by hand 3 or 4 turns before tightening firmly 1 Coat here with refrigerating machine oil Mounting the air inlet panel with a canvas connection See figure 7b 1 Ceiling surface 2 Ceiling opening 3 Air inlet panel Optional accessory 4 Indoor unit Back side 5 Canvas connection for air inlet panel Optional accessory Model A FH Y B35 45 760 FH ...

Page 8: ...cket adding water from water inlet 5 Drain outlet for maintenance with rubber drain plug 6 Refrigerant pipes NOTE The drain outlet is only used to discharge water if the drain pump is not used or before maintenance Gently put in and out the drain plug Excessive force may deform the drain socket of the drain pan WHEN ELECTRIC WIRING WORK IS FINISHED Check drainage flow during COOL running explained...

Page 9: ...y from power supply wiring Not following this guideline may result in malfunction due to electrical noise 4 For the remote controller wiring refer to the Installation manual of the remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only specified wires and tigh...

Page 10: ...UB MAIN SUB CHANGEOVER 1 Insert a wedge head screwdriver into the recess between the upper and lower part of the remote controller and working from the 2 positions pry off the upper part see figure 13 The remote controller PC board is attached to the upper part of the remote controller 2 Turn the main sub changeover switch on one of the two remote controller PC boards to S see figure 18 Leave the ...

Page 11: ... M1F EMBEDDED F1U FUSE 250V 5A H1P H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN M1F MOTOR FAN M1P MOTOR DRAIN PUMP R1T THERMISTOR AIR R2T THERMISTOR COIL RyC MAGNETIC RELAY OUTDOOR UNIT COMPRESSOR RyF1 4 MAGNETIC RELAY FAN RyP MAGNETIC RELAY DRAIN PUMP SS1 SELECTOR SWITCH EMERGENCY X1M X2M TERMINAL STRIP RC SIGNAL RECEIVER CIRCUIT TC SIGNAL TRANSMISSION CIRCUIT WIRED REMOTE CONTROLLER BS1 ON OFF...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE08271 1A ...

Reviews: