background image

5

Electrical characteristics

Model

Hz

Volts

Voltage range

FH(Y)B35~125

50

230

min.198-max.264

NOTE 

For details, refer to "Electrical data".

Specifications for field supplied wires

Connection

Wire

Size

between indoor units

H05VV-U4G

2mm

2

unit-remote controller

Shielded wire (2)

0.75-1.25mm

2

NOTE 

For details, refer to the chapter "Wiring example".

Use H07RN-F as wiring between indoor units in case of no
protection.

Allowable length of transmission wiring between the indoor unit
and the remote controller is max. 500m.

WIRING EXAMPLE AND HOW TO SET THE
REMOTE CONTROLLER

How to connect wiring

From the outside of the unit

Remove the switch box cover as shown in figure 11b, and make
the connections.

From the inside of the unit

Remove the small bottom plate and the interchangeable plate (in
case of rear suction) or the air filter holding plate (in case of
bottom suction). Lower the switch box as shown in figure 11c.
Put the wires through the wiring ports of the switch box cover
before connecting them.

1

Small bottom plate

2

Air filter holding plate

3

Switch box

4

Interchangeable plate

5

Square hole (covered by the switch box cover)

PRECAUTIONS

1 Observe the notes mentioned below when wiring to the power

supply terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

2 Do not connect wires of different gauge to the same

grounding terminal. Looseness in the connection may
deteriorate the protection.

3 Remote controller cords and wires connecting the units

should be located at least 50mm away from power supply
wiring. Not following this guideline may result in malfunction
due to electrical noise.

4 For the remote controller wiring, refer to the "Installation

manual of the remote controller" supplied with the remote
controller.

5 Never connect the power supply wiring to the terminal board

for transmission wiring. This mistake could damage the entire
system.

6 Use only specified wires and tightly connect wires to the

terminals. Be careful that wires do not place external stress
on the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the switch
box cover. Make sure the cover closes tight. Incomplete
connections could result in overheating, and in the worse
case, electric shock or fire.

7 Ground the shield of the shield wire of the remote controller

cord to the earth screw inside the switch box.

WIRING EXAMPLE

Fit the power supply wiring of each system with a switch and
fuse as shown in figure 14.

1

Power supply

2

Main switch

3

Fuse

4

Outdoor unit

5

Indoor unit

6

Remote controller (optional accessory)

COMPLETE SYSTEM EXAMPLE (3 systems)

When using 1 remote controller for 1 indoor unit (normal
operation) (see figure 14)

For group control (see figure 16)

Use with 2 remote controllers (see figure 15)

NOTE

It is not necessary to designate an indoor unit address when
using group control. The address is automatically set when
the power is activated.

PRECAUTIONS

1. A single switch can be used to supply power to units on the

same system. However, branch switches and branch circuit
breakers must be selected carefully.

2. For a group control remote controller, choose the remote

controller that suits the indoor unit which has the most
functions.

3. Do not ground the equipment on gas pipes, water pipes,

lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

Summary of Contents for FHYB100FK7V1

Page 1: ...Split System air conditioners INSTALLATION MANUAL FHYB35Fk7V1 FHYB45Fk7V1 FHYB60Fk7V1 FHYB71Fk7V1 FHYB100Fk7V1 FHYB125Fk7V1 FHB35Fk7V1 FHB45Fk7V1 FHB60Fk7V1 ...

Page 2: ...standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning är utförd i överensstämmelse med och följer följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgi...

Page 3: ...0 1 4 3 4 2 800 630 B A 145 2 5 6 7 4 3 2 3 1 4 680 85 1 3 2 4 6 5 50 200 45 680 1 5 2 3 7 4 680 65 5 1 2 3 2 4 460 180 A 160 160 300 425 4 2 2 3 1 460 180 350 A 1 100mm 3 2 1 6 5 4 1 3 2 2 1 3 1 3 2 4 5 2 1 2 3 1 1 5m 0 625mm 2 6 1 5 4 A 3 ...

Page 4: ...12 11a 11b 11c 3 5 1 2 4 2 2 1 1 2 S M S S M 1 2 3 5 4 1 3 2 9 11 12 6 7 9 6 12 8 10 5 EMERG NORM 15 14 17 18 13 16 1 2 3 4 5 6 1 2 3 4 5 6 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 ...

Page 5: ...of the outdoor unit for items not described in this manual Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machi...

Page 6: ...nce for maintenance and service can be ensured Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the outdoor unit Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical appliances Noise may be...

Page 7: ...utside with refrigerating machine oil and initially tighten by hand 3 or 4 turns before tightening firmly 1 Coat here with refrigerating machine oil Mounting the air inlet panel with a canvas connection See figure 7b 1 Ceiling surface 2 Ceiling opening 3 Air inlet panel Optional accessory 4 Indoor unit Back side 5 Canvas connection for air inlet panel Optional accessory Model A FH Y B35 45 760 FH ...

Page 8: ...cket adding water from water inlet 5 Drain outlet for maintenance with rubber drain plug 6 Refrigerant pipes NOTE The drain outlet is only used to discharge water if the drain pump is not used or before maintenance Gently put in and out the drain plug Excessive force may deform the drain socket of the drain pan WHEN ELECTRIC WIRING WORK IS FINISHED Check drainage flow during COOL running explained...

Page 9: ...y from power supply wiring Not following this guideline may result in malfunction due to electrical noise 4 For the remote controller wiring refer to the Installation manual of the remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only specified wires and tigh...

Page 10: ...UB MAIN SUB CHANGEOVER 1 Insert a wedge head screwdriver into the recess between the upper and lower part of the remote controller and working from the 2 positions pry off the upper part see figure 13 The remote controller PC board is attached to the upper part of the remote controller 2 Turn the main sub changeover switch on one of the two remote controller PC boards to S see figure 18 Leave the ...

Page 11: ... M1F EMBEDDED F1U FUSE 250V 5A H1P H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN M1F MOTOR FAN M1P MOTOR DRAIN PUMP R1T THERMISTOR AIR R2T THERMISTOR COIL RyC MAGNETIC RELAY OUTDOOR UNIT COMPRESSOR RyF1 4 MAGNETIC RELAY FAN RyP MAGNETIC RELAY DRAIN PUMP SS1 SELECTOR SWITCH EMERGENCY X1M X2M TERMINAL STRIP RC SIGNAL RECEIVER CIRCUIT TC SIGNAL TRANSMISSION CIRCUIT WIRED REMOTE CONTROLLER BS1 ON OFF...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE08271 1A ...

Reviews: