background image

6

External static pressure Mode No.

FIRST CODE No.

SECOND CODE No.

13 (23)

6

01

02

03

Standard: 49 Pa

(5mm H

2

O)

High static

pressure:

88/108 Pa

(9/11mm H

2

O)

Low static

pressure: 20 Pa

(2mm H

2

O)

(NOTE)

Setting

Air filter

contamination-

light

Air filter

contamination-

heavy

Spacing time

of display air filter sign

(long life type)

Approx. 2500 hrs

Approx. 1250 hrs

FIRST

CODE No.

0

Mode No.

10 (20)

SECOND

CODE

No.

01

02

F

IELD

 S

ETTING

Field setting must be made from the remote controller in
accordance with the installation condition.

Setting can be made by changing the "Mode number", "First
CODE No." and "SECOND CODE No".

For setting and operation, refer to the "FIELD SETTING" in
the installation manual of the remote controller.

Setting of static pressure

Change the SECOND CODE No. according to Table 3
depending on the resistance of the connection duct.

NOTE 

Low static pressure is only able to set for FH(Y)B35•45•60,
FHYB71.

The unit is factory set for standard static pressure (SECOND
CODE No. 01) at the time of skipping.

Setting air filter sign

Remote controllers are equipped with liquid crystal display air
filer signs to display the time to clean air filters.

Change the SECOND CODE No. According to Table 4
depending on the amount of dirt or dust in the room.
(SECOND CODE No. Is factory set to "01" for filter
contamination-light.)

Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN"

 and the other to "SUB".

MAIN/SUB CHANGEOVER

1. Insert a wedge-head screwdriver into the recess between the

upper and lower part of the remote controller and, working
from the 2 positions, pry off the upper part. (see figure 13)
(The remote controller PC board is attached to the upper part
of the remote controller.)

2. Turn the main/sub changeover switch on one of the two

remote controller PC boards to "S". (see figure 18)
(Leave the switch of the other remote controller set to "M".)

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

INSTALLATION OF THE DECORATION PANEL

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no
space between the unit body and decoration panel.

TEST OPERATION

Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE
SPECIAL CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED".

After finishing the construction of refrigerant piping, drain
piping, and electric wiring, conduct test operation accordingly
to protect the unit.

1. Open the gas side stop valve.
2. Open the liquid side stop valve.
3. Electrify crank case heater for 6 hours. (Not necessary for the

straight cooling type)

4. Set to cooling operation with the remote controller and start

operation by pushing ON/OFF button.

5. Press Inspection/Test Operation button 4 times and operate

at Test Operation mode for 3 minutes.

6. Press Inspection/Test Operation button and operate normally.
7. Confirm function of unit according to the operation manual.

PRECAUTIONS

In case something is wrong with the unit and it does not operate,
refer to the malfunction diagnosis label attached to the unit.

Summary of Contents for FHYB100FK7V1

Page 1: ...Split System air conditioners INSTALLATION MANUAL FHYB35Fk7V1 FHYB45Fk7V1 FHYB60Fk7V1 FHYB71Fk7V1 FHYB100Fk7V1 FHYB125Fk7V1 FHB35Fk7V1 FHB45Fk7V1 FHB60Fk7V1 ...

Page 2: ...standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning är utförd i överensstämmelse med och följer följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgi...

Page 3: ...0 1 4 3 4 2 800 630 B A 145 2 5 6 7 4 3 2 3 1 4 680 85 1 3 2 4 6 5 50 200 45 680 1 5 2 3 7 4 680 65 5 1 2 3 2 4 460 180 A 160 160 300 425 4 2 2 3 1 460 180 350 A 1 100mm 3 2 1 6 5 4 1 3 2 2 1 3 1 3 2 4 5 2 1 2 3 1 1 5m 0 625mm 2 6 1 5 4 A 3 ...

Page 4: ...12 11a 11b 11c 3 5 1 2 4 2 2 1 1 2 S M S S M 1 2 3 5 4 1 3 2 9 11 12 6 7 9 6 12 8 10 5 EMERG NORM 15 14 17 18 13 16 1 2 3 4 5 6 1 2 3 4 5 6 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 ...

Page 5: ...of the outdoor unit for items not described in this manual Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machi...

Page 6: ...nce for maintenance and service can be ensured Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the outdoor unit Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical appliances Noise may be...

Page 7: ...utside with refrigerating machine oil and initially tighten by hand 3 or 4 turns before tightening firmly 1 Coat here with refrigerating machine oil Mounting the air inlet panel with a canvas connection See figure 7b 1 Ceiling surface 2 Ceiling opening 3 Air inlet panel Optional accessory 4 Indoor unit Back side 5 Canvas connection for air inlet panel Optional accessory Model A FH Y B35 45 760 FH ...

Page 8: ...cket adding water from water inlet 5 Drain outlet for maintenance with rubber drain plug 6 Refrigerant pipes NOTE The drain outlet is only used to discharge water if the drain pump is not used or before maintenance Gently put in and out the drain plug Excessive force may deform the drain socket of the drain pan WHEN ELECTRIC WIRING WORK IS FINISHED Check drainage flow during COOL running explained...

Page 9: ...y from power supply wiring Not following this guideline may result in malfunction due to electrical noise 4 For the remote controller wiring refer to the Installation manual of the remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only specified wires and tigh...

Page 10: ...UB MAIN SUB CHANGEOVER 1 Insert a wedge head screwdriver into the recess between the upper and lower part of the remote controller and working from the 2 positions pry off the upper part see figure 13 The remote controller PC board is attached to the upper part of the remote controller 2 Turn the main sub changeover switch on one of the two remote controller PC boards to S see figure 18 Leave the ...

Page 11: ... M1F EMBEDDED F1U FUSE 250V 5A H1P H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN M1F MOTOR FAN M1P MOTOR DRAIN PUMP R1T THERMISTOR AIR R2T THERMISTOR COIL RyC MAGNETIC RELAY OUTDOOR UNIT COMPRESSOR RyF1 4 MAGNETIC RELAY FAN RyP MAGNETIC RELAY DRAIN PUMP SS1 SELECTOR SWITCH EMERGENCY X1M X2M TERMINAL STRIP RC SIGNAL RECEIVER CIRCUIT TC SIGNAL TRANSMISSION CIRCUIT WIRED REMOTE CONTROLLER BS1 ON OFF...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE08271 1A ...

Reviews: