background image

 

 

 

Installation and operation manual

 

3

 

FDYMP71~125L7V1

Split System air conditioners

4PW14036-1B

 

I

 

NDOOR

 

 

 

UNIT

 

 

 

INSTALLATION

 

When installing optional accessories read also the installation
manual of the optional accessories. Depending on the field
conditions, it may be easier to install optional accessories before the
indoor unit is installed.

 

1.

Install the indoor unit temporarily.

 

Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. 

(See figure 2)

 

2.

Check if the unit is horizontally levelled.

 

If the unit is tilted against condensate flow, condensate water
could drip out of the unit.

Check if the unit is levelled at all four corners with a water
level or a water-filled vinyl tube as shown in 

figure 3

.

 

3.

Tighten the upper nut.

 

R

 

EFRIGERANT

 

 

 

PIPING

 

 

 

WORK

 

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

 

 

Use a pipe cutter and flare suitable for the used refrigerant.

 

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand
before tightening firmly.

Check the pipe connector for gas leaks, then insulate it.

D

RAIN

 

PIPING

 

WORK

1

Install the drain pipes.

-

Keep piping as short as possible and slope it downwards so 
that air may not remain trapped inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe.

-

For connection to the drain socket: use a flexible hose (field 
supply) and clamp it firmly. This to avoid leaks due to 
operating vibration of the unit.

-

After clamping, isolate the drain socket. This is to avoid leaks 
due to sweating of the unit.

-

Do not use a trap in the drain piping.

-

Never put the end of the drain hose into water.

2

Insulate the drain hose inside the building.

3

Drain check

-

Execute the drain check before installing the duct

-

Make sure that the drain hose is firmly connected

-

Pour some water into the drain pan to check if the water flows 
smoothly.

1

Nut (field supply)

2

Washer for hanger bracket (field supply)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

NOTE

Required service opening dimensions for air filter
maintenance (See 

figure 1

 and 

figure 4

)

NOTE

All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

W

Width of service opening

D

Depth of service opening

h

Distance unit-false ceiling

Model

W

D

FDYMP71•100

920

If h

30 

⇒ 

D

100

FDYMP125

1320

If h>30 

⇒ 

D

200

2

3

1

4

Pipe 

gauge

Tightening torque

Flare 

dimension A 

(mm)

Flare shape

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.0~12.4

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

18.6~19.0

Ø19.1

97.2~118.6 N•m 

(990~1210 kgf•cm)

22.9~23.3

Coat here with ether oil 
or ester oil

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid line (field 
supply). The insulation should 
withstand 80°C.

4

Insulation for fitting of gas line (field 
supply). The insulation should 
withstand 120°C.

5

Clamps (use 2 clamps per insulation)

1

Metal clamp

2

Flexible hose

3

Insulation

4

Plastic clamp

R=0.4~0.8

45

° ±

2

90

°±

4

A

3

4

1

2

5

1

4

2

3

Summary of Contents for FDYMP71L7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1 Split System air conditioners...

Page 2: ...25 10 43 5 46 18 35 12 25 18 35 12 25 RP71 125 RYP71 125 RYEP71 125 RYP71 125 RYEP71 125 1 2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 6 1 2 3 1 2 3 1 2 3 4 5 P1 P2 1 2 3 1 2 3 1 2 3 4 5 P1 P2 P1 P2 M S S 1 X40A 1...

Page 3: ...tt anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes...

Page 4: ...ere volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves can be found Control system may malfunction Where the air contains high levels of salt such...

Page 5: ...e figure 6 For other installation than standard installation contact your Daikin dealer for details 2 The fan speed for this indoor unit is preset to provide high external static pressure If lower ext...

Page 6: ...insulate it DRAIN PIPING WORK 1 Install the drain pipes Keep piping as short as possible and slope it downwards so that air may not remain trapped inside the pipe Keep pipe size equal to or greater th...

Page 7: ...e remote controller supplied with the remote controller 5 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 6 Use only spe...

Page 8: ...f Table 4 TEST OPERATION Refer to the section of For the following items take special care during construction and check after installation is finished on page 2 After finishing the construction of re...

Page 9: ...when not using for long periods of time Electricity is consumed as long as the switch is on Turn off the main power supply switch in order to save energy Turn on the main power supply switch 6 hours b...

Page 10: ...this noise Dust from the units Dust may blow out from the unit after starting operation from long resting time Dust absorbed by the unit blows out The units give off odours The unit absorbs the smell...

Page 11: ...emove any obstacle Check if the earth is connected Clean the air filter After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN14036 1B...

Reviews: