Installation manual

3

FDY(P)125~2 FDQ125B7V3B

Split System air conditioners

4PW10621-1C

V

ACUUM

 

DRYING

 

OF

 

INSTALLATION

Refer to the installation manual of the outdoor unit.

D

RAIN

 

PIPING

 

WORK

D

RAIN

 

CHECK

Make sure that the drain hose is firmly connected. Put some water
into the drain pan to check if the water flows smoothly.

F

IELD

 

WIRING

Use copper wire only.

For electric wiring work, refer also to 

"Internal wiring - parts

table" on page 5

.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.

Refer to table below for specifications of field wire.

Methods of wiring units and connecting remote 
controller cords 

(Refer to 

figure 6

)

Wiring the units (Power supply wiring).

Connect the interconnection wiring (from outdoor to indoor) to
the 1-2-3 terminal (1) using a separate power supply wire to
connect to power supply of the indoor unit fan motor to the L-N
terminal.

Remote controller code.
Connect the cords to the remote controller terminal (P1, P2) (No
Polarity) (2).

Precautions

Do not clamp remote controller cords together with the other
wiring. Doing so may cause malfunction.

Remote controller cords and wires connecting the units should
be located at least 50 mm from other electric wires. Not following
this guideline may result in malfunction due to electrical noise.

Observe the notes mentioned below when wiring to the power supply
terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure below.

Wiring example

Pair type (Refer to 

figure 7

)

Remote controller controls 1 indoor unit (standard system).

Control by two remote controllers (Refer to 

figure 8

)

Two remote controllers control 1 indoor unit.

Group control (Refer to 

figure 9

)

Remote controller controls up to 16 indoor units.

(All indoor units operate according to the remote controller.)

The drain hose must slope downward to the outdoor
side.

Never put the end of the drain into water.

A trap to prevent bad odours is allowed.

If you extend the drain hose always insulate it up to the
outdoor side with polyethylene foam insulation material
(field supplied).

To ensure a downward slope of minimum 1:100, install
hanging bars every 1 to 1.5 m.

If unifying multiple drain pipes, install pipes shown in
the figure above.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant local
and national regulations.

The field wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.

Be sure to use a dedicated power circuit. 

Never use a power supply shared by another appliance.

Size (mm

2

)

Length

Interconnection wire

H05VV-U4G (Note)

1

Unit remote controller

Sheathed wire (2 wires)

0.75~1.25

Max. 500 m

Power supply indoor fan

Must comply with relevant local and national regulations

The table above presents the specifications of field wiring
to be applied in case of protected pipes are used. Use
HO5RN-F in case of no protection.

100

1

Main power supply

2

Main switch

3

Fuse

4

Outdoor unit

5

Indoor unit

6

Remote controller

7

Remote controller (Optional accessories)

NOTE

1.

All transmission wiring except for the remote
controller wires must match the terminal symbol.

2.

Use shield wire in transmission wiring. Ground the

shield of the shield wire to “

”, at the grounding

screw of the remote controller cord grounding
terminal inside the control box.

3.

For group control remote controller, choose the
remote controller that suits the indoor unit which
has the most functions (as attached swing flap).

Summary of Contents for FDQ125B7V3B x 2

Page 1: ...INSTALLATION MANUAL FDY125B7V1 FDY200B7V1 FDY250B7V1 FDYP125B7V1 FDYP200B7V1 FDYP250B7V1 FDQ125B7V3B Split System air conditioners ...

Page 2: ... 1 2 2 1 4 5 3 2 1 4 1440 602 125 class 840 200 250 class P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 P1 P2 P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 7 P1 P2 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 1 2 3 4 5 6 7 8 9 ...

Page 3: ...menttien vaatimuksia edellyttäen että niitä käytetään ohjeidemme mukaisesti following the provisions of Directives as amended gemäß den Vorschriften der Direktiven gemäß Änderung conformément aux stipulations des Directives telles que modifiées overeenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas según lo enmendado secondo le prescrizioni per Dir...

Page 4: ... there is a risk reinforce the ceiling before installing the unit CHECK LIST For the following items take special care during construction and check after installation is finished FDY P 125B7V1 FDQ125B7V3B FDY P 200B7V1 FDY P 250B7V1 Split System air conditioners Installation manual READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPE...

Page 5: ...d refrigerant The liquid line must be connected to the air conditioning unit via a flare connection The gas line must be welded directly to the air conditioning unit piping In case of a FDY125 unit both the liquid line and the gas line must be connected to the air conditioning via a flare connection In case of flare connections flare the pipe end neatly to avoid refrigerants leaks Be sure to use b...

Page 6: ...g example Pair type Refer to figure 7 Remote controller controls 1 indoor unit standard system Control by two remote controllers Refer to figure 8 Two remote controllers control 1 indoor unit Group control Refer to figure 9 Remote controller controls up to 16 indoor units All indoor units operate according to the remote controller The drain hose must slope downward to the outdoor side Never put th...

Page 7: ...de n according to the table to enable or disable the remote sensor TEST OPERATION Refer to Check list on page 1 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the re...

Page 8: ...l adaptor X30A Connector interface adaptor for Sky Air series only for FDY P 125 250 X33A Connector Adaptor for wiring X40A Connector remote on off forced off X60A X61A Connector interface adaptor for Sky Air series only for FDQ Wired remote controller BS2 Timer mode start stop button BS7 Timer on off button BS3 BS8 Programming timer button BS1 ON OFF button BS4 Temperature setting button up BS6 O...

Page 9: ...NOTES NOTES ...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN10621 1C ...

Reviews: