FDY(P)125~2 FDQ125B7V3B
Split System air conditioners
4PW10621-1C

Installation manual

4

F

IELD

 

SETTING

Setting external static pressure

Depending on the external static pressure (ducts, filter, etc.) which is
connected to the air conditioning unit the fan speed should be set by
changing the wires in the switch box. (Refer to 

figure 5

)

Factory set:

fan speed is 

M

.

High ESP:

fan speed is 

H

.

Low ESP: 

fan speed is 

L

.

Setting air filter sign

Remote controllers are equipped with liquid crystal display air
filter signs to display the time to clean air filters.

Change the SECOND CODE No. according to the table
depending on the amount of dirt or dust in the room. (SECOND
CODE No. is factory set to “01” for filter contamination-light.)

Setting the remote sensor

The customer has the ability to select the thermistor. Both unit and
remote controller are equipped with a thermistor.

Setting

Change the second code n° according to the table to enable or
disable the remote sensor.

T

EST

 

OPERATION

Refer to 

"Check list" on page 1

.

After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.

1.

Open the gas side stop valve.

2.

Open the liquid side stop valve.

3.

Electrify crank case heater for 6 hours.

4.

Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.

5.

Press Inspection/Test Operation button 4 times and operate at
Test Operation mode for 3 minutes.

6.

Press Inspection/Test Operation button and operate normally.

7.

Confirm function of unit according to the operation manual.

Precautions

In case something is wrong with the unit and it does not operate, refer
to the malfunction diagnosis label attached to the unit.

NOTES

Setting

Spacing time of

display air filter sign 

(long life type)

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Air filter contamination-light

±2500 hrs

10 (20)

0

01

Air filter contamination-heavy

±1250 hrs

02

Setting

Mode n°

1st code n°

2nd code n°

Enabled

20

2

01

Disabled

20

2

02

Summary of Contents for FDQ125B7V3B x 2

Page 1: ...INSTALLATION MANUAL FDY125B7V1 FDY200B7V1 FDY250B7V1 FDYP125B7V1 FDYP200B7V1 FDYP250B7V1 FDQ125B7V3B Split System air conditioners ...

Page 2: ... 1 2 2 1 4 5 3 2 1 4 1440 602 125 class 840 200 250 class P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 P1 P2 P1 P2 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 7 P1 P2 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 1 2 3 P2 1 2 3 L N P1 2 3 1 4 5 3 2 6 1 2 3 4 5 6 7 8 9 ...

Page 3: ...menttien vaatimuksia edellyttäen että niitä käytetään ohjeidemme mukaisesti following the provisions of Directives as amended gemäß den Vorschriften der Direktiven gemäß Änderung conformément aux stipulations des Directives telles que modifiées overeenkomstig de bepalingen van Richtlijnen zoals geamendeerd siguiendo las disposiciones de Directivas según lo enmendado secondo le prescrizioni per Dir...

Page 4: ... there is a risk reinforce the ceiling before installing the unit CHECK LIST For the following items take special care during construction and check after installation is finished FDY P 125B7V1 FDQ125B7V3B FDY P 200B7V1 FDY P 250B7V1 Split System air conditioners Installation manual READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPE...

Page 5: ...d refrigerant The liquid line must be connected to the air conditioning unit via a flare connection The gas line must be welded directly to the air conditioning unit piping In case of a FDY125 unit both the liquid line and the gas line must be connected to the air conditioning via a flare connection In case of flare connections flare the pipe end neatly to avoid refrigerants leaks Be sure to use b...

Page 6: ...g example Pair type Refer to figure 7 Remote controller controls 1 indoor unit standard system Control by two remote controllers Refer to figure 8 Two remote controllers control 1 indoor unit Group control Refer to figure 9 Remote controller controls up to 16 indoor units All indoor units operate according to the remote controller The drain hose must slope downward to the outdoor side Never put th...

Page 7: ...de n according to the table to enable or disable the remote sensor TEST OPERATION Refer to Check list on page 1 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit 1 Open the gas side stop valve 2 Open the liquid side stop valve 3 Electrify crank case heater for 6 hours 4 Set to cooling operation with the re...

Page 8: ...l adaptor X30A Connector interface adaptor for Sky Air series only for FDY P 125 250 X33A Connector Adaptor for wiring X40A Connector remote on off forced off X60A X61A Connector interface adaptor for Sky Air series only for FDQ Wired remote controller BS2 Timer mode start stop button BS7 Timer on off button BS3 BS8 Programming timer button BS1 ON OFF button BS4 Temperature setting button up BS6 O...

Page 9: ...NOTES NOTES ...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN10621 1C ...

Reviews: