SiSG121917E
Wall Mounted and LSP Duct Type Functions
Part 4 Functions and Control
54
Note
Application range is as follows.
The sensor may not detect moving objects further than 7 m away. (Please see the
application range)
Sensor detection sensitivity changes according to the indoor unit location, the speed of
passers-by, temperature range, etc.
The sensor could also mistakenly detect pets, sunlight, fluttering curtains and light reflected
off of mirrors as passers-by.
INTELLIGENT EYE operation will not switch on during POWERFUL operation.
NIGHT SET mode will not switch on during use of INTELLIGENT EYE operation.
1.12 POWERFUL Operation
Outline
In order to exploit the cooling capacity to full extent, the air conditioner can be operated by
increasing the indoor fan rotating speed and the compressor frequency.
Details
When
POWERFUL
button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Ex: POWERFUL operation in cooling
A = 40 ~ 80 rpm (depending on the model)
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW, or
OUTDOOR UNIT QUIET operation.
90°
55°
7m
55°
Vertical angle 90°
(Side
v
ie
w
)
Horizontal
angle 110°
(Top
v
ie
w
)
7m
(R25176)
Operation mode
Fan speed
Target temperature
COOL
H tap +
A
rpm
18°C
DRY
Dry rotating speed +
A
rpm
Lowered by 2 ~ 2.5°C
FAN
H tap +
A
rpm
—
(R24808)
Target temp.
Fan
A
rpm
18˚C
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF