SiUS091601EA
Functions for FTX, FVXS Series
Part 4 Functions and Control
56
2.9 INTELLIGENT EYE Operation
Applicable
Models
FTX18/24UVJU
Outline
The microcomputer detects the presence of humans in the room with a motion sensor and reduces
the capacity when there is nobody in the room in order to save electricity.
Details
1. INTELLIGENT EYE detection method
The motion sensor detects human motion by receiving infrared rays and sends the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. If the motion sensor
detects 10 times or more of the wave output in one second in total, and the High signal
continues for 3 sec., the microcomputer judges humans are in the room as the human detection
signal is ON.
2. Motions (in cooling)
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
When there is no signal from the motion sensor in 20 minutes, the microcomputer judges that
nobody is in the room and operates the unit at a temperature shifted from the target
temperature. (Cooling/Dry: 1 ~ 2°C (1.8 ~ 3.6°F) higher, Heating: 2°C (3.6°F) lower, Auto:
according to the operation mode at that time)
1 sec.
Sampling (20 msec.)
High
Low
ON
OFF
High
Low
(R24035)
(Condition of 10 times or more output)
Human motion
3 sec.
If the detection signal (High) continues for 3 sec. or more,
the microcomputer judges humans are in the room.
Detection signal
from the motion
sensor
Human detection
signal
Motion sensor
output
If the motion sensor detects the outputs
10 times/sec. or more, the microcomputer
judges the detection signal from the
motion sensor is High.
ON
OFF
Reset
Reset
Reset
20 min.
1 ~ 2°C (1.8 ~ 3.6 °F)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
#
)
Set speed
Set speed
Target temperature
(R23920)
Remote controller
Sensor
button
Human detection
signal
↑
↑
60 rpm
↑
within
20 min.
within
20 min.
within
20 min.
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...