42
English
R3 FDM36PEVLK
RY3 FDYM36PEVLK
Outdoor
Unit
L
N
L
(1)
(2)
(3)
C
R
Y
O
B
N
L1
N1
L
N
breaker
PE
PE
C
Y
Indoor
Unit
Outdoor
Unit
L
N
L
(1)
(2)
(3)
C
R
Y
O
C
R
Y
O
B
N
L1
N1
L
N
breaker
PE
PE
Indoor
Unit
POWER 220V ~ 60HZ
(1) Power Cord 3 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 2 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
POWER 220V ~ 60HZ
(1) Power Cord 3 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 4 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
R4 FDM42PEVLK
R4 FDM48PEVLK
RY4 FDYM42PEVLK
RY4 FDYM48PEVLK
Outdoor
Unit
L
N
L
N
L1
(1)
(2)
(3)
C
R
Y
O
B
L2
L3
N
L2
L3
breaker
L1
PE
C
Y
Indoor
Unit
Outdoor
Unit
L
N
L1
(1)
(2)
(3)
C
R
Y
O
B
L
N
C
R
Y
O
L2
L3
N
L2
L3
breaker
L1
PE
Indoor
Unit
POWER 220V 3 ~ 60HZ
(1) Power Cord 4 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 2 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A
POWER 220V 3 ~ 60HZ
(1) Power Cord 4 × 6.0mm² (H07RN-F)
(2) Power Cord 3 × 1.0mm² (H07RN-F)
(3) Communication Cords 4 × 1.0mm² (H07RN-F)
Capability of Breaker: 32A