11Tr Outdoor Unit Field Wiring Instruction:
1q> Power
Supply to indoor
unit
Field Earth Wire
1q> to indoor & 3q>
Power Supply Field
Wire
Note:
•
(LV)Communication
Wire to indoor unit
1. Minimum 25mm or more gap to be maintained between High Voltage(HV) and Low Voltage (LV) wires
during field installation.
2. For Indoor to outdoor communication, use only 2 core shielded cable of 0.5 mm
2
for field wiring.
11.
OIL REFILL CHARGE GUIDELINES
1. In case of majority Oil spill/Loss by Leakage in field ------
Remove all remaning oil from the compressor.
A
dd fresh oil charge in the compressor as per below table.
Indoor
Outdoor
Refill oil charge
ltr/30m pipe length
FDKR200AV16
RZR200AY16
1.656
FDKR300AV16
RZR300AY16
2.395
FDKR400AV16
RZR400AY16
2.632
OIL REMOVIN
G PROCEDURE :
1.
To remove all remaining oil from the compressor, first remove compressor from the system.
T
ake it out side & tilt in such a way so that all oil can come outside from suction port.
Note :
Check
q
uality of oil, if oil color is clear (not black or turbide), use same oil for refilling & top up fresh
oil to maintain total refill
q
uantity as per above table. If oil color is not clear, do not use this oil, refill with
fresh oil only.
OIL REFILL PROCEDURE :
1. Charge oil through the suction port of compressor.
13