background image

Outdoor Unit RZR200AY16 Horizontal Air Discharge 

co 

Ii) 

1060 

1100 

Outdoor Unit RZR300AY16 Horizontal Air Discharge 

C) 

rn 

O"' 

r--

0::, 

rn 

1236 

1200 

1276 

Outdoor Unit RZR400AY16 Horizontal Air Discharge 

r-­

rn 

-.j-

1688 

106 

All dimensions are in mm 

All dimensions are in mm 

N<Xl 

'° 

;:,!: 

All dimensions are in mm 

Summary of Contents for FDKR200AV16

Page 1: ...DAIKIN INSTALLATION MANUAL OPERATION MANUAL CEILING CONCEALED SPLIT TYPE AIR CONDITIONER FDKR200AV16 FDKR300AV16 FDKR400AV16 3P724053 2...

Page 2: ...10 6 Electrical Wiring Work 11 13 7 Oil Refill Charge Guidelines 13 8 Vacuuming and Charging 14 9 Special Precautions when charging Unit with Scroll Compressor 15 10 Standard Operating Conditions 16 1...

Page 3: ...ling R41 OA contains no chlorine does not destroy the ozone layer and so does not reduce the earth s protection against harmful ultraviolet radiations R41 OA will contribute only slightly to the green...

Page 4: ...pipe for indoor unit after brazing 2 Use M10 M12 rods for installation of Indoor units total Number of installation rods should be in accordance with number of hanger metal provided for installation C...

Page 5: ...wind A place where the air discharge and operating sound level will not annoy the neighbours The location must not be susceptible to dust or oil mist Location For Installation Of The Condensing Units...

Page 6: ...ge air from another to avoid hot air short cycling This also applies when two or more units are installed one above the other Below are the installation clearance guidelines Model RZR200AY16 A mm 500...

Page 7: ...0 0 LO co 3_7 _8 3 3 _ 4_6_2 i i t co 0 o Nr N Indoor Unit FDKR300AV16 0 0 r CX 0 I I H I 342 330 1760 1660 1458 1077 316 10 HOLE 07 I 330 342 J 8 O N A LO LO N 275x3 825 12 HOLE 07 6 M LO N 0 O N M A...

Page 8: ...Indoor Unit FDKR400AV16 1804 1647 All dimensions are in mm 1211 338 330 330 391 312 30 N 151 en N MCC I LO LO I N 14 HOLE r 7 880 30 940 7...

Page 9: ...ge co Ii N 1060 1100 Outdoor Unit RZR300AY16 Horizontal Air Discharge C rn O r 0 rn 1236 1200 1276 Outdoor Unit RZR400AY16 Horizontal Air Discharge r rn j 1688 8 106 All dimensions are in mm All dimen...

Page 10: ...2 5 27 8 RZR400AY16 40 131 2 8 4 Caution 1 Our guarantee on performance of our air conditioners is strictly revoked if the height length and or the number of bends of the refrigerant piping system in...

Page 11: ...pipe stage by stage advancing the blade of the pipe cutter slowly Extra force and deep cut will cause more distortion on the pipe and thus extra burr See figure Remove burrs from cut edges of the pipe...

Page 12: ...ted solidly and rigid in position 2 Piping and connectionsare leak proof after charging 3 Proper wiring has been done see fig below Drainage check Pour some water into left side of drain pan drainage...

Page 13: ...er Supply Field Wire 8 5Tr Outdoor Unit Field Wiring Instruction lq Power Supply to indoor unit Clamp for LV Communication Wire LV Communication Wire to indoor unit 12 Clamp for LV Communication Wire...

Page 14: ...ssor Add fresh oil charge in the compressor as per below table Indoor Outdoor Refill oil charge ltr 30m pipe length FDKR200AV16 RZR200AY16 1 656 FDKR300AV16 RZR300AY16 2 395 FDKR400AV16 RZR400AY16 2 6...

Page 15: ...ples and replace caps Precautions while charging i Refrigerant cannot be charged until field wiring has been completed ii Refrigerant may only be charged after performing the leak test and vacuum dryi...

Page 16: ...ect charge has been weighed in If additional charge is required start the system and slowly bleed liquid into the suction side until the system is full It is recommended tocharge liquid refrigerant in...

Page 17: ...eaner or wash in lukewarm water below 40 C with a neutral cleaning detergent 2 Rinse the filter well and dry before placing it back onto the unit 3 Do not use gasoline volatile substances or chemicals...

Page 18: ...irements Your air conditioning product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted household waste Do not try to dismantle the system...

Page 19: ...uld be the cause Consult your local dealer for assistance The refrigerant used for the air conditioner is safe and normally does not leak However if the refrigerant leaks and gets in contact with a na...

Page 20: ...et The containers may explode because the warm air from the indoor or outdoor unit will affect them Turn off the main power switch when the air conditioner is not to be used for prolonged periods When...

Page 21: ...complete drainage If drain piping is not carried out properly drain will not flow out Then dirt and debris may be accumulated in the drain piping and may cause water leakage If it occurs stop the air...

Page 22: ...conditioner with less running noises and vibrations b A place where the hot wind discharged from theair outlet of the outdoor unit and the running noises do not cause a nuisance to neighbours Are you...

Page 23: ...windows remain open room air will flow out and decrease the effect of cooling and heating Never place objects near the air inlet and the air outlet of the air conditioner It maydecrease the effect or...

Page 24: ...pad If lock is activated ON OFF FAN SPEED MODE RESET CANCEL and MENU key will be active and Menu Mode will have only options to unlock keypad If invalid key is pressed on lock activation 0 symbol flas...

Page 25: ...R of Timer will start that it blinking On press LEFT RIGHT key switch between HOUR MINUTES Blinking of hour minute can be changed by UP DOWN Key b On set cancel on timer OFF TIME symbol will get ON an...

Page 26: ...protection Outdoor Unit H9 Outdoor air thermistor system malfunction Outdoor Unit J3 Discharge piping temperature malfunction Outdoor Unit J5 Suction piping thermistor system malfunction Outdoor Unit...

Page 27: ...gh fan speed 6 Water flowing out from the air conditioner unit 7 Hissing air flow sound from the air conditioner unit Switch off the unit and call dealer Refrigerant fluid flowing into the evaporator...

Page 28: ...DAIKIN AIRCONDIT ON NG IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase 111 Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P724053 2...

Reviews: