INSTALLATION CLEARANCE
When two or more outdoor units are installed in a location, they must be positioned such that one unit will not be
taking the hot discharge air from another to avoid hot air short cycling.This also applies when two or more units
are installed one above the other. Below are the installation clearance guidelines:
Model
RZR200AY16
A(mm)
500
B (mm)
750
C(mm)
1200
D (mm)
1000
Horizontal air discharge
LEGEND
-- SPACE FOR AIR FLOW
SPACE FOR SERVICE
RZR300AY16
RZR400AY16
500
700
750
1000
1200
1200
1000
1000
5