![background image](http://html.mh-extra.com/html/daikin/fdb10cxv1/fdb10cxv1_technical-manual_2460385093.webp)
90
Performance Data
Model: FDYM28CXV1 - RY30DXV1
Heating Mode
ID DB
Outdoor WB
-9°C
-6°C
-5°C
6°C
12°C
15°C
18°C
TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
15°C
3.942
3.942
4.829
4.829
5.125
5.125
8.381
8.381
10.157 10.157 11.045 11.045 11.933 11.933
17°C
3.868
3.868
4.740
4.740
5.030
5.030
8.379
8.379
9.882
9.882
10.738 10.738 11.594 11.594
19°C
3.795
3.795
4.650
4.650
4.935
4.935
8.376
8.376
9.606
9.606
10.430 10.430 11.255 11.255
21°C
3.722
3.722
4.560
4.560
4.839
4.839
8.374
8.374
9.330
9.330
10.123 10.123 10.915 10.915
23°C
3.690
3.690
4.480
4.480
4.744
4.744
7.941
7.941
9.054
9.054
9.815
9.815
10.576 10.576
25°C
3.658
3.658
4.401
4.401
4.648
4.648
7.508
7.508
8.779
8.779
9.508
9.508
10.237 10.237
27°C
3.627
3.627
4.321
4.321
4.553
4.553
7.076
7.076
8.503
8.503
9.200
9.200
9.897
9.897
Frost Region
Remark:
AFR: Air
fl
ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2.
shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
DAIKIN_R22 CC.indb 90
DAIKIN_R22 CC.indb 90
11/8/2012 11:40:17 AM
11/8/2012 11:40:17 AM
Summary of Contents for FDB10CXV1
Page 2: ......
Page 134: ...131 Wiring Diagrams Indoor Unit Model FDM15CXV1 FDB15CXV1 Outdoor Unit Model R15CXV1 ...
Page 135: ...132 Wiring Diagrams Indoor Unit Model FDM20 25CXV1 FDB20 25CXV1 Outdoor Unit Model R20 25CXV1 ...
Page 136: ...133 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R28CXV1 ...
Page 137: ...134 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXV1 ...
Page 138: ...135 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXY1 ...
Page 139: ...136 Wiring Diagrams Indoor Unit Model FDM38 40CXV1 FDB40CXV1 Outdoor Unit Model R35 40DXV1 ...
Page 141: ...138 Wiring Diagrams Indoor Unit Model FDM60CXV1 FDB60CXV1 Outdoor Unit Model R61DXY1 ...
Page 143: ...140 Wiring Diagrams Indoor Unit Model FDYM15CXV1 FDYB15CXV1 Outdoor Unit Model RY15CXV1 ...
Page 145: ...142 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY28CXV1 ...
Page 146: ...143 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXV1 ...
Page 147: ...144 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXY1 ...
Page 148: ...145 Wiring Diagrams Indoor Unit Model FDYM38 40CXV1 FDYB40CXV1 Outdoor Unit Model RY35 40DXV1 ...
Page 150: ...147 Wiring Diagrams Indoor Unit Model FDYM60CXV1 FDYB60CXV1 Outdoor Unit Model RY61DXY1 ...
Page 159: ......