![background image](http://html.mh-extra.com/html/daikin/fdb10cxv1/fdb10cxv1_technical-manual_2460385057.webp)
54
Engineering & Physical Data
Engineering Data - R22 MODEL
MODEL
INDOOR UNIT
FDB60CXV1
OUTDOOR UNIT
R61DXY1
NOMINAL COOLING CAPACITY
Btu/h
56000
W
16410
NOMINAL TOTAL INPUT POWER (COOLING)
W
5800
NOMINAL RUNNING CURRENT (COOLING)
A
9.83
EER
W/W
2.89
REFRIGERANT CONTROL (EXPANSION DEVICE)
INDOOR CAP. TUBE
REFRIGERANT CHARGE
kg
5.00
MODEL
INDOOR UNIT
FDYB60CXV1
OUTDOOR UNIT
RY61DXY1
NOMINAL COOLING CAPACITY
Btu/h
56000
W
16410
NOMINAL HEATING CAPACITY
Btu/h
56000
W
16410
NOMINAL TOTAL INPUT POWER (COOLING)
W
5884
NOMINAL TOTAL INPUT POWER (HEATING)
W
4854
NOMINAL RUNNING CURRENT (COOLING)
A
9.83
NOMINAL RUNNING CURRENT (HEATING)
A
8.63
EER
W/W
2.85
COP
W/W
3.46
REFRIGERANT CONTROL (EXPANSION DEVICE)
INDOOR & OUTDOOR
CAP. TUBE
REFRIGERANT CHARGE
kg
5.00
POWER SOURCE
V/Ph/Hz
380 - 415 / 3 / 50
REFRIGERANT TYPE
R22
INDOOR UNIT
CONTROL
AIR DISCHARGE
DUCTED
OPERATION
SLM WIRED HANDSET
AIR FLOW
SUPER HIGH
l/s / CFM
802 / 1700
HIGH
l/s / CFM
765 / 1620
MEDIUM
l/s / CFM
717 / 1520
LOW
l/s / CFM
694 / 1470
EXTERNAL STATIC PRESSURE (H/M/L)
Pa (in.wg.)
69 / 49 / 29 / 20
(0.28 / 0.20 / 0.12 / 0.08)
SOUND PRESSURE LEVEL (H/M/L)
dBA
48 / 47 / 46 / 45
UNIT DIMENSION
HEIGHT X WIDTH X DEPTH
mm
378 x 1499 x 541
PACKING DIMENSION
HEIGHT X WIDTH X DEPTH
mm
415 x 1701 x 631
UNIT WEIGHT
kg
62
CONDENSATE DRAIN SIZE
mm
19.1
FAN
TYPE
CENTRIFUGAL
DRIVE
DIRECT
FAN MOTOR
TYPE
INDUCTION
INDEX OF PROTECTION (IP)
IP 20
INSULATION GRADE
CLASS B
RATED INPUT POWER
W
558
RATED RUNNING CURRENT
A
2.43
MOTOR OUTPUT
W
300
POLES
4
COIL
TUBE
MATERIAL
COPPER
DIAMETER
mm
9.52
FIN
MATERIAL
ALUMINIUM
FACE AREA
m
2
0.47
ROW
3
AIR QUALITY
FILTER
TYPE
WASHABLE SARANET
FILTER
QUANTITY
pc
2
CASING
COLOUR
WITHOUT POWDER
PAINT
OUTDOOR UNIT
AIR FLOW
l/s / CFM
1793 / 3800
SOUND PRESSURE LEVEL
dBA
61
UNIT DIMENSION
HEIGHT X WIDTH X DEPTH
mm
852 x 1030 x 400
PACKING DIMENSION
HEIGHT X WIDTH X DEPTH
mm
1010 x 1180 x 514
UNIT WEIGHT
kg
108
PIPE
CONNECTION
TYPE
FLARE VALVE
SIZE
LIQUID
mm
12.70
GAS
mm
19.05
FAN
TYPE
PROPELLER
DRIVE
DIRECT
FAN MOTOR
TYPE
INDUCTION
INDEX OF PROTECTION (IP)
IP 54
INSULATION GRADE
CLASS F
RATED INPUT POWER
W
272
RATED RUNNING CURRENT
A
1.28
MOTOR OUTPUT
W
145
POLES
8
COMPRESSOR
TYPE
SCROLL
OIL TYPE
MINERAL
(Sontex 200 LT)
OIL AMOUNT
cm
3
1705
R
RATED INPUT POWER (COOLING)
W
4970
RATED RUNNING CURRENT
(COOLING)
A
8.59
RY
RATED INPUT POWER (COOLING)
W
5054
RATED INPUT POWER (HEATING)
W
4024
RATED RUNNING CURRENT
(COOLING)
A
8.59
RATED RUNNING CURRENT
(HEATING)
A
7.39
LOCKED ROTOR AMP.
A
74
COIL
TUBE
MATERIAL
COPPER
R
DIAMETER
mm
9.52
RY
DIAMETER
mm
9.52
FIN
MATERIAL
ALUMINIUM
FACE AREA
m
2
0.84
ROW
3
CASING
COLOUR
LIGHT GREY
ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
COOLING
HEATING
INDOOR: 27°C DB / 19°C WB
INDOOR: 20°C DB
OUTDOOR: 35°C DB / 24°C WB
OUTDOOR: 7°C DB / 6°C WB
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_R22 CC.indb 54
DAIKIN_R22 CC.indb 54
11/8/2012 11:40:09 AM
11/8/2012 11:40:09 AM
Summary of Contents for FDB10CXV1
Page 2: ......
Page 134: ...131 Wiring Diagrams Indoor Unit Model FDM15CXV1 FDB15CXV1 Outdoor Unit Model R15CXV1 ...
Page 135: ...132 Wiring Diagrams Indoor Unit Model FDM20 25CXV1 FDB20 25CXV1 Outdoor Unit Model R20 25CXV1 ...
Page 136: ...133 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R28CXV1 ...
Page 137: ...134 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXV1 ...
Page 138: ...135 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXY1 ...
Page 139: ...136 Wiring Diagrams Indoor Unit Model FDM38 40CXV1 FDB40CXV1 Outdoor Unit Model R35 40DXV1 ...
Page 141: ...138 Wiring Diagrams Indoor Unit Model FDM60CXV1 FDB60CXV1 Outdoor Unit Model R61DXY1 ...
Page 143: ...140 Wiring Diagrams Indoor Unit Model FDYM15CXV1 FDYB15CXV1 Outdoor Unit Model RY15CXV1 ...
Page 145: ...142 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY28CXV1 ...
Page 146: ...143 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXV1 ...
Page 147: ...144 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXY1 ...
Page 148: ...145 Wiring Diagrams Indoor Unit Model FDYM38 40CXV1 FDYB40CXV1 Outdoor Unit Model RY35 40DXV1 ...
Page 150: ...147 Wiring Diagrams Indoor Unit Model FDYM60CXV1 FDYB60CXV1 Outdoor Unit Model RY61DXY1 ...
Page 159: ......