108
Performance Data
Model: FDYM40CXV1 - RY35DXV1 / FDYB40CXV1 - RY35DXV1
Heating Mode
ID DB
Outdoor WB
-9°C
-6°C
-5°C
6°C
12°C
15°C
18°C
TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
15°C
4.651
4.651
5.850
5.850
6.249
6.249
10.644 10.644 13.041 13.041 14.239 14.239 15.438 15.438
17°C
4.527
4.527
5.729
5.729
6.129
6.129
10.445 10.445 12.685 12.685 13.842 13.842 14.999 14.999
19°C
4.404
4.404
5.608
5.608
6.009
6.009
10.247 10.247 12.329 12.329 13.445 13.445 14.560 14.560
21°C
4.280
4.280
5.487
5.487
5.890
5.890
10.049 10.049 11.974 11.974 13.047 13.047 14.121 14.121
23°C
4.278
4.278
5.397
5.397
5.770
5.770
9.698
9.698
11.618 11.618 12.650 12.650 13.682 13.682
25°C
4.276
4.276
5.306
5.306
5.650
5.650
9.347
9.347
11.262 11.262 12.252 12.252 13.243 13.243
27°C
4.274
4.274
5.216
5.216
5.530
5.530
8.997
8.997
10.906 10.906 11.855 11.855 12.804 12.804
Frost Region
Remark:
AFR: Air
fl
ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2.
shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.
DAIKIN_R22 CC.indb 108
DAIKIN_R22 CC.indb 108
11/8/2012 11:40:20 AM
11/8/2012 11:40:20 AM
Summary of Contents for FDB10CXV1
Page 2: ......
Page 134: ...131 Wiring Diagrams Indoor Unit Model FDM15CXV1 FDB15CXV1 Outdoor Unit Model R15CXV1 ...
Page 135: ...132 Wiring Diagrams Indoor Unit Model FDM20 25CXV1 FDB20 25CXV1 Outdoor Unit Model R20 25CXV1 ...
Page 136: ...133 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R28CXV1 ...
Page 137: ...134 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXV1 ...
Page 138: ...135 Wiring Diagrams Indoor Unit Model FDM28 30CXV1 FDB30CXV1 Outdoor Unit Model R30DXY1 ...
Page 139: ...136 Wiring Diagrams Indoor Unit Model FDM38 40CXV1 FDB40CXV1 Outdoor Unit Model R35 40DXV1 ...
Page 141: ...138 Wiring Diagrams Indoor Unit Model FDM60CXV1 FDB60CXV1 Outdoor Unit Model R61DXY1 ...
Page 143: ...140 Wiring Diagrams Indoor Unit Model FDYM15CXV1 FDYB15CXV1 Outdoor Unit Model RY15CXV1 ...
Page 145: ...142 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY28CXV1 ...
Page 146: ...143 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXV1 ...
Page 147: ...144 Wiring Diagrams Indoor Unit Model FDYM28 30CXV1 FDYB30CXV1 Outdoor Unit Model RY30DXY1 ...
Page 148: ...145 Wiring Diagrams Indoor Unit Model FDYM38 40CXV1 FDYB40CXV1 Outdoor Unit Model RY35 40DXV1 ...
Page 150: ...147 Wiring Diagrams Indoor Unit Model FDYM60CXV1 FDYB60CXV1 Outdoor Unit Model RY61DXY1 ...
Page 159: ......