5 Installation

Installation and operation manual

6

250AXVEB

Split system air conditioners

3P580564-1 – 2019.04

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.

≥100

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Pull out the drain plug.

2

Install the adapter for the drain hose (field supply).

3

Push the drain hose as far as possible over the adapter for the
drain hose.

4

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

5

Check  for  water  leaks  (see 

"To  check  for  water  leaks"  on

page 6

).

6

Install the insulation piece (drain pipe).

b

a

c

d

e

a

Indoor unit

b

BSP 1" internal thread

c

Adapter (field supply)

d

Metal clamp (field supply)

e

Insulation material for drain pipe (field supply)

To check for water leaks

Gradually  pour  approximately  1  l  of  water  in  the  drain  pan,  and
check for water leaks.

a

b

c d

a

Container with water

b

Drain pan

c

Drain outlet

d

Refrigerant pipes

5.1.3

Guidelines when installing the ducting

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  A

min

specified in the General safety precautions;

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ an air inlet or outlet is connected directly with a room by

ducting. Do NOT use spaces such as a false ceiling as
a duct for the air inlet or outlet.

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"7.1 Field setting" on page 9

).

The ducting is to be field supplied.

1

Attach the flange (located on the unit) using 45 screws for duct
flanges (accessory).

2

Connect the canvas duct to the inside of the flange.

3

Connect the duct to the canvas duct.

4

Wind  aluminium  tape  around  the  flange  and  duct  connection.
Make sure there are no air leaks at any other connection.

Summary of Contents for FDA200AXVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA200AXVEB FDA250AXVEB...

Page 2: ...na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus normi...

Page 3: ...Symptom The units can give off odours 15 14 1 6 Symptom The display shows 88 15 14 1 7 Symptom The operation stopped suddenly Operation lamp is on 15 14 1 8 Symptom The outdoor fan rotates while the a...

Page 4: ...er bracket d Screws for duct flanges M5 12 e Hexagon head bolt M10 40 f Attached piping with sealing g Tie wrap h Spring washer 3 About the units and options 3 1 System layout INFORMATION The followin...

Page 5: ...e the ceiling before installing the unit Suspension bolts Use M10 suspension bolts for installation Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer from the upp...

Page 6: ...o the unit using a duct system make sure there are no operating ignition sources example open flames an operating gas appliance or an operating electric heater in case the floor area is less than Amin...

Page 7: ...ction attached to the unit d Indoor unit 2 Connect the gas piping using the attached piping accessory Fix it to the unit using hexagon head bolts M10 40 accessory and spring washers accessory Place se...

Page 8: ...each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each o...

Page 9: ...the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside o...

Page 10: ...ailable on the Daikin extranet authentication required 9 1 Wiring diagram 9 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is...

Page 11: ...H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ Connection connector For the user 10 About the system INFORMATION This appliance is intended to be used by expert or trained...

Page 12: ...nual of the installed user interface 12 Operation 12 1 Operation range For combination with R410A outdoor unit refer to the following table Outdoor units Cooling Heating RZQ200 250 Outdoor temperature...

Page 13: ...clean filter notification Clean the air filter when the notification is displayed If the dirt becomes impossible to clean change the air filter How to clean the air filter 1 Remove the screws on the...

Page 14: ...ation and shut off the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electric shock or fire Contact your dealer The system MU...

Page 15: ...the outdoor unit will stop operation and the indoor unit will operate in fan only mode low fan speed In case of multi split the indoor unit alternately operates in fan stop mode and fan only mode LL l...

Page 16: ...ers 3P580564 1 2019 04 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P580564 1 2019 04 Copyright 2019 Daikin...

Reviews: