Daikin FDA200AXVEB Installation And Operation Manual Download Page 5

5 Installation

Installation and operation manual

5

250AXVEB
Split system air conditioners
3P580564-1 – 2019.04

≥300

d

 470

≥20

e

 ≥790

≥2500

b

c

a

 ≥1143

a

 ≥650

A

B

(mm)

A

Top view

B

Side view

a

Service space

b

Ceiling

c

Floor surface

d

Minimum required space of installation

e

Space needed to maintain a downward slope of at least
1/100. 

"5.1.2 Guidelines when installing the drain

piping" on page 5

.

5

Installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

5.1

Mounting the indoor unit

5.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

Suspension  bolts.

  Use  M10  suspension  bolts  for  installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

Ceiling opening size. 

Make sure the ceiling opening is within the

following limits:

1100
1028

1490

1526

 

d

 ≥650

 

d

 ≥1143

±150

(mm)

e

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

d

Service space

e

Inspection hatch (600×600 mm)

Installation example:

b

a

c

e

d

a

Anchor

b

Ceiling slab

c

Long nut or turn-buckle

d

Suspension bolt

e

Indoor unit

Install the unit temporarily.

1

Attach the hanger bracket to the suspension bolt.

2

Fix it securely.

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Water level

b

Vinyl tube

3

Tighten the upper nut.

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the drain piping side is raised), water may drip.

5.1.2

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

Summary of Contents for FDA200AXVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA200AXVEB FDA250AXVEB...

Page 2: ...na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus normi...

Page 3: ...Symptom The units can give off odours 15 14 1 6 Symptom The display shows 88 15 14 1 7 Symptom The operation stopped suddenly Operation lamp is on 15 14 1 8 Symptom The outdoor fan rotates while the a...

Page 4: ...er bracket d Screws for duct flanges M5 12 e Hexagon head bolt M10 40 f Attached piping with sealing g Tie wrap h Spring washer 3 About the units and options 3 1 System layout INFORMATION The followin...

Page 5: ...e the ceiling before installing the unit Suspension bolts Use M10 suspension bolts for installation Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer from the upp...

Page 6: ...o the unit using a duct system make sure there are no operating ignition sources example open flames an operating gas appliance or an operating electric heater in case the floor area is less than Amin...

Page 7: ...ction attached to the unit d Indoor unit 2 Connect the gas piping using the attached piping accessory Fix it to the unit using hexagon head bolts M10 40 accessory and spring washers accessory Place se...

Page 8: ...each other In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each o...

Page 9: ...the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside o...

Page 10: ...ailable on the Daikin extranet authentication required 9 1 Wiring diagram 9 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is...

Page 11: ...H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ Connection connector For the user 10 About the system INFORMATION This appliance is intended to be used by expert or trained...

Page 12: ...nual of the installed user interface 12 Operation 12 1 Operation range For combination with R410A outdoor unit refer to the following table Outdoor units Cooling Heating RZQ200 250 Outdoor temperature...

Page 13: ...clean filter notification Clean the air filter when the notification is displayed If the dirt becomes impossible to clean change the air filter How to clean the air filter 1 Remove the screws on the...

Page 14: ...ation and shut off the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage electric shock or fire Contact your dealer The system MU...

Page 15: ...the outdoor unit will stop operation and the indoor unit will operate in fan only mode low fan speed In case of multi split the indoor unit alternately operates in fan stop mode and fan only mode LL l...

Page 16: ...ers 3P580564 1 2019 04 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P580564 1 2019 04 Copyright 2019 Daikin...

Reviews: