5 Configuration

Installation and operation manual

9

FCAHG71~140HVEB
Split system air conditioners
4P535639-1B – 2019.01

If the distance to the floor is (m)

Then

1

FCAHG71

FCAHG100~140

M

C1

C2

≤2.7

≤3.2

13 (23)

0

01

2.7<x≤3.0

3.2<x≤3.6

02

3.0<x≤3.5

3.6<x≤4.2

03

Setting: Decoration panel type

When  installing  or  changing  the  decoration  panel  type,  ALWAYS
check if the correct values are set.

If the … decoration panel is used

Then

1

M

C1

C2

Standard or self-cleaning

13

(23)

15

01

Design

02

Setting: Air flow direction

This setting must correspond with the actual used air flow directions.
See  the  installation  manual  of  the  optional  blocking  pad  kit  and  the
manual of the user interface.

Default: 01 (= all-round air flow)

Example: 

1

2

3

4

1

2

3

4

1

2

3

a

b

c

a

All-round air flow

b

4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)

c

3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the air volume speed:

If you want

Then

1

Outdoor unit

M

C1

C2

General

3MXM, 4MXM,

5MXM

During cooling
operation

LL

2

12

(22)

6

01

Setup volume

2

02

During heating
operation

LL

2

Monitoring 1

2

12

(22)

3

01

Setup volume

2

Monitoring 2

2

02

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

1

M

C1

C2

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

No notification

3

02

Individual setting in a simultaneous operation system

We  recommend  using  the  optional  user  interface  to  set  the  slave
unit.

Perform the following steps:

2

Change  the  second  code  number  to  02  to  perform  individual
setting on the slave unit.

If you want to set the slave unit as…

Then

1

M

C1

C2

Unified setting

21(11)

01

01

Individual setting

02

3

Perform field setting for the master unit.

4

Turn off the main power supply switch.

5

Disconnect  the  remote  controller  from  the  master  unit  and
connect it to the slave unit.

6

Change to individual setting.

7

Perform field setting for the slave unit.

8

Turn off the main power supply or, in case of more slave units,
repeat the previous steps for all slave units.

9

Disconnect the user interface from the slave unit and reconnect
it to the master unit.

It  is  not  necessary  to  rewire  the  remote  controller  from  the  master
unit  if  the  optional  user  interface  is  used.  (However,  remove  the
wires  attached  to  the  user  interface  terminal  board  of  the  master
unit)

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

(2)

Fan speed:

LL

: Low fan speed

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button

on the user interface.

Monitoring  1,  2

:  The  fan  is  OFF,  but  runs  for  a  short  time  every  6  minutes  to  detect  the  room  temperature  by  Low  fan

speed (1) or by Setup volume (2).

Summary of Contents for FCAHG71HVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Page 2: ...abljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus...

Page 3: ...culation airflow 14 12 5 1 To start the active circulation airflow 14 13 Maintenance and service 15 13 1 Precautions for maintenance and service 15 13 2 Cleaning the air filter suction grille air outl...

Page 4: ...n 70 dBA CAUTION Appliance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial a...

Page 5: ...4 a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine...

Page 6: ...accessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condens...

Page 7: ...are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly...

Page 8: ...h the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the un...

Page 9: ...ification is displayed on the user interface When using a wireless user interface you must also set the address see the installation manual of the user interface If you want an interval of air contami...

Page 10: ...amaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves...

Page 11: ...cked E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The a...

Page 12: ...N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC Thermistor PTC Q Insulated gate bipolar trans...

Page 13: ...12 Operation 12 1 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation In combination with R410A outdoor units Outdoor units Cooling Heating...

Page 14: ...flow units For the following conditions a micro computer controls the air flow direction which may be different from the display Cooling Heating When the room temperature is lower than the set tempera...

Page 15: ...f If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devices make sure to...

Page 16: ...sible consequence Discoloration and deformation Do NOT scrub firmly when washing the blade with water Possible consequence The surface sealing peels off Clean with a soft cloth If it is difficult to r...

Page 17: ...hich the refrigerant leaked has been repaired 14 Troubleshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off th...

Page 18: ......

Page 19: ......

Page 20: ...4P535639 1B 2019 01 Copyright 2018 Daikin...

Reviews: