4 Installation

Installation and operation manual

6

FCAHG71~140HVEB

Split system air conditioners

4P535639-1B – 2019.01

Level

. Make sure the unit is level at all 4 corners using a level or a

water-filled vinyl tube.

c

b

b

a

a

Level

b

Vinyl tube

c

Water level

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

4.1.2

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤675  mm  perpendicular

to the unit.

≤675

≤300

0~75

1000~1500

(mm)

b

a

b

c

a

d

d

a

Metal clamp (accessory)

b

Drain hose (accessory)

c

Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)

d

Hanging bars (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure  to  use  drain  pipes  and  T-joints  with  a  correct  gauge  for  the
operating capacity of the units.

≥100

675

(mm)

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check  for  water  leaks  (see 

"To  check  for  water  leaks"  on

page 6

).

4

Install the insulation piece (drain pipe).

5

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with cable ties.

6

Connect the drain piping to the drain hose.

≤4 mm

A

A'

A-A'

A

A'

f

6

5

2

c

e

4

b

a

d

b

a

d

c

3

1

2~6

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Insulation piece (drain pipe) (accessory)

f

Drain piping (field supply)

To check for water leaks

The  procedure  differs  depending  on  whether  electrical  wiring  is
already finished. When electrical wiring is not finished yet, you need
to  temporarily  connect  the  user  interface  and  power  supply  to  the
unit.

When electrical wiring is not finished yet

1

Temporarily connect electrical wiring.

Summary of Contents for FCAHG71HVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Page 2: ...abljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus...

Page 3: ...culation airflow 14 12 5 1 To start the active circulation airflow 14 13 Maintenance and service 15 13 1 Precautions for maintenance and service 15 13 2 Cleaning the air filter suction grille air outl...

Page 4: ...n 70 dBA CAUTION Appliance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial a...

Page 5: ...4 a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine...

Page 6: ...accessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condens...

Page 7: ...are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly...

Page 8: ...h the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the un...

Page 9: ...ification is displayed on the user interface When using a wireless user interface you must also set the address see the installation manual of the user interface If you want an interval of air contami...

Page 10: ...amaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves...

Page 11: ...cked E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The a...

Page 12: ...N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC Thermistor PTC Q Insulated gate bipolar trans...

Page 13: ...12 Operation 12 1 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation In combination with R410A outdoor units Outdoor units Cooling Heating...

Page 14: ...flow units For the following conditions a micro computer controls the air flow direction which may be different from the display Cooling Heating When the room temperature is lower than the set tempera...

Page 15: ...f If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devices make sure to...

Page 16: ...sible consequence Discoloration and deformation Do NOT scrub firmly when washing the blade with water Possible consequence The surface sealing peels off Clean with a soft cloth If it is difficult to r...

Page 17: ...hich the refrigerant leaked has been repaired 14 Troubleshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off th...

Page 18: ......

Page 19: ......

Page 20: ...4P535639 1B 2019 01 Copyright 2018 Daikin...

Reviews: