4 Installation

Installation and operation manual

5

FCAG35~140BVEB
Split system air conditioners
4P535626-1C – 2019.09

4

Installation

4.1

Mounting the indoor unit

4.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

In  case  of  installation  with  a  fresh  air  intake  kit

.  Install  the

fresh air intake kit always 

before

 installing the unit.

Decoration  panel

.  Install  the  decoration  panel  always 

after

installing the unit.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

A

c

b

d
e

a

A

50~100 mm

: In case of installation with standard panel

100~150 mm

: In case of installation with fresh air intake kit

or design panel

130~180 mm

: In case of installation with self-cleaning

decoration panel

a

Ceiling slab

b

Anchor

c

Long nut or turnbuckle

d

Suspension bolt

e

Suspended ceiling

Suspension bolts.

 Use M8~M10 suspension bolts for installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

(mm)

780

710

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centers.  You  can  attach
the paper pattern to the unit.

a

c

b

d

a

Centre of the unit

b

Centre of the ceiling opening

c

Paper pattern for installation (upper part of the packing)

d

Screws (accessories)

Ceiling opening and unit

:

▪ Make sure the ceiling opening is within the following limits:

Minimum

: 860 mm to be able to fit the unit.

Maximum

:  910  mm  to  ensure  enough  overlap  between  the

decoration  panel  and  the  suspended  ceiling.  If  the  ceiling
opening is larger, add extra ceiling material.

▪ Make  sure  the  unit  and  its  hanger  brackets  (suspension)  are

centered within the ceiling opening.

(mm)

710
840
860~910

950

c
d

e
f

780

840

860~910

950

c

d e

f

a

b

a

Drain piping

b

Refrigerant piping

c

Hanger bracket pitch (suspension)

d

Unit

e

Ceiling opening

f

Decoration panel

Example

If A

Then

B

C

A

C

B

860 mm

10 mm

45 mm

910 mm

35 mm

20 mm

A

Ceiling opening

B

Distance between the unit and the ceiling opening

C

Overlap between the decoration panel and the suspended
ceiling

Installation  guide

.  Use  the  installation  guide  to  determine  the

correct vertical position.

2

1

2

1

2
1

2
1

A

B

1

1

2

C

a b c

2

1

2

D

A

In case of installation with standard decoration panel

B

In case of installation with fresh air intake kit

C

In case of installation with self-cleaning decoration panel

D

In case of installation with design decoration panel

a

Suspended ceiling

b

Installation guide (accessory)

c

Unit

Summary of Contents for FCAG35BVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35BVEB FCAG50BVEB FCAG60BVEB FCAG71BVEB FCAG100BVEB FCAG125BVEB FCAG...

Page 2: ...ojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurody...

Page 3: ...tion airflow 14 12 5 1 To start the active circulation airflow 14 13 Maintenance and service 15 13 1 Precautions for maintenance and service 15 13 2 Cleaning the air filter suction grille air outlet a...

Page 4: ...from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment Spacing Mind the following requirements mm 1500 2000 4000 1500 A B C b...

Page 5: ...Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine the...

Page 6: ...mp accessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against cond...

Page 7: ...ted of materials that are inherently resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Re...

Page 8: ...h the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the un...

Page 9: ...e installation manual of the user interface If you want an interval of air contamination Then 1 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneou...

Page 10: ...terface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backlight To perform an ON OFF action o...

Page 11: ...ical wires Error code Possible cause U4 or UF The inter unit branch wiring is not correct UA The outdoor and indoor unit are incompatible 7 Disposal NOTICE Do NOT try to dismantle the system yourself...

Page 12: ...ixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing s...

Page 13: ...ty ranges for safe and effective operation In combination with R410A outdoor units Outdoor units Cooling Heating RR71 125 15 46 C DB 12 28 C WB RQ71 125 5 46 C DB 10 15 C WB 12 28 C WB 10 27 C DB RXS3...

Page 14: ...the dry program The function of this program is to decrease the humidity in your room with minimal temperature decrease minimal room cooling The micro computer automatically determines temperature an...

Page 15: ...or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand and fitting for damage If damaged the uni...

Page 16: ...air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on for 10 min then...

Page 17: ...em is odourless WARNING R410A is a non combustible refrigerant and R32 is a mildly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes into contact with fire...

Page 18: ......

Page 19: ......

Page 20: ...4P535626 1C 2019 09 Copyright 2018 Daikin...

Reviews: