background image

7 Disposal

Installation and operation manual

11

FCAG35~140BVEB
Split system air conditioners
4P535626-1C – 2019.09

#

Action

Result

2

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

3

Press.

The unit returns to normal
operation, and the home
menu is displayed.

6.3

Error codes when performing a
test run

If  the  installation  of  the  outdoor  unit  has  NOT  been  done  correctly,
the following error codes may be displayed on the user interface:

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  or  indoor  unit

PCB has blown.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

Error code

Possible cause

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

7

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

8

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

8.1

Piping diagram: Indoor unit

b

a

c

a

Liquid pipe connection

b

Gas pipe connection

c

Heat exchanger

8.2

Wiring diagram

8.2.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit.  Part  numbering  is  by  Arabic  numbers  in  ascending  order  for
each part and is represented in the overview below by "*" in the part
code.

Symbol

Meaning

Symbol

Meaning

Circuit breaker

Protective earth

Connection

Protective earth
(screw)

,

Connector

A

Rectifier

Earth

Relay connector

Field wiring

Short-circuit
connector

Fuse

Terminal

INDOOR

Indoor unit

Terminal strip

OUTDOOR

Outdoor unit

Wire clamp

Symbol

Colour

Symbol

Colour

BLK

Black

ORG

Orange

BLU

Blue

PNK

Pink

BRN

Brown

PRP, PPL

Purple

GRN

Green

RED

Red

GRY

Grey

WHT

White

YLW

Yellow

Symbol

Meaning

A*P

Printed circuit board

BS*

Pushbutton ON/OFF, operation
switch

BZ, H*C

Buzzer

C*

Capacitor

AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*

Connection, connector

D*, V*D

Diode

DB*

Diode bridge

Summary of Contents for FCAG35BVEB

Page 1: ...tion and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAG35BVEB FCAG50BVEB FCAG60BVEB FCAG71BVEB FCAG100BVEB FCAG125BVEB FCAG...

Page 2: ...ojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurody...

Page 3: ...tion airflow 14 12 5 1 To start the active circulation airflow 14 13 Maintenance and service 15 13 1 Precautions for maintenance and service 15 13 2 Cleaning the air filter suction grille air outlet a...

Page 4: ...from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment Spacing Mind the following requirements mm 1500 2000 4000 1500 A B C b...

Page 5: ...Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine the...

Page 6: ...mp accessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against cond...

Page 7: ...ted of materials that are inherently resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly flammable Re...

Page 8: ...h the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the un...

Page 9: ...e installation manual of the user interface If you want an interval of air contamination Then 1 M C1 C2 2500 h light 10 20 0 01 1250 h heavy 02 No notification 3 02 Individual setting in a simultaneou...

Page 10: ...terface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backlight To perform an ON OFF action o...

Page 11: ...ical wires Error code Possible cause U4 or UF The inter unit branch wiring is not correct UA The outdoor and indoor unit are incompatible 7 Disposal NOTICE Do NOT try to dismantle the system yourself...

Page 12: ...ixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing s...

Page 13: ...ty ranges for safe and effective operation In combination with R410A outdoor units Outdoor units Cooling Heating RR71 125 15 46 C DB 12 28 C WB RQ71 125 5 46 C DB 10 15 C WB 12 28 C WB 10 27 C DB RXS3...

Page 14: ...the dry program The function of this program is to decrease the humidity in your room with minimal temperature decrease minimal room cooling The micro computer automatically determines temperature an...

Page 15: ...or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand and fitting for damage If damaged the uni...

Page 16: ...air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on for 10 min then...

Page 17: ...em is odourless WARNING R410A is a non combustible refrigerant and R32 is a mildly flammable refrigerant they normally don t leak If the refrigerant leaks in the room and comes into contact with fire...

Page 18: ......

Page 19: ......

Page 20: ...4P535626 1C 2019 09 Copyright 2018 Daikin...

Reviews: