background image

7

English

3. Install the suspension bolts. (Refer to Fig. 2)

(Use M10 size bolt for the suspension bolt)
Use anchors for existing ceilings, and a sunken insert, 
sunken anchor or other field supplied parts for new ceil-
ings to reinforce the ceiling to bear the weight of the unit.

NOTE

All the above parts are field supplied.

5. INDOOR UNIT INSTALLATION

<When installing optional accessories (except for the decoration panel), read also the installation 
manual for optional accessories.
Depending on the field conditions, it may be easier to install optional accessories before the indoor 
unit is installed.>

Be sure to use the furnished accessories or ones that match the specifications when installing.

1. Install the indoor unit temporarily.

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer (8) from the upper 
and lower sides of the hanger bracket. 

(Refer to Fig. 3)

2. Check the unit is horizontally level.

 

(Refer to Fig. 4)

CAUTION

The indoor unit is equipped with a built-in drain pump and float switch. Verify that it is level by using a level 

or a water-filled vinyl tube.

(If the unit is tilted against condensate flow, the float switch may malfunction and cause water to drip.)

3. Tighten the upper nut.

4. Fix the installation paper pattern

The paper pattern for installation corre-
sponds with the measurements of the ceil-
ing opening. Consult the builder for details.

Attach the paper pattern for installation to 
the unit with the attached screws. 

(Refer to Fig. 5)

The paper pattern for installation is marked 
for 3 types of ceiling openings. Read the 
notations carefully when installing.

Ceiling slab

Long nut or 
turn-buckle

Suspension bolt

Indoor unit

<Installation example>

Anchor

Fig. 2

Field supply

(8)Washer for hanger
     bracket (attached)

Tighten (double nuts)

Fig. 3

Vinyl tube

Level

Fig. 4

(2) Paper pattern 
      for installation 
      (attached)

(11) Screws for fixing 
        the paper pattern 
        for installation 
        (×6 attached)

Fig. 5

01_EN_3P156215-4C.fm  Page 7  Saturday, May 14, 2005  9:17 AM

Summary of Contents for FBQ60BV1

Page 1: ...FBQ60BV1 FBQ60BVL FBQ71BV1 FBQ71BVL SPLIT SYSTEM Air Conditioners INSTALLATION MANUAL READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE 00_C...

Page 2: ...caution may result in injury or damage to the equipment WARNING Ask your dealer or qualified personnel to carry out installation work Do not try to install the air conditioner yourself Improper instal...

Page 3: ...aves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireless kit transmitting distance can result shorter than expected in rooms with elec tronic fluoresce...

Page 4: ...de Where volatile flammable gas like thinner or gasoline is used Where machines can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as tha...

Page 5: ...35 cm or more Installation not required Items to be checked If not properly done what is likely to occur Check Are the indoor unit and outdoor unit fixed firmly The unit may drop vibrate or make noise...

Page 6: ...e gas leakage Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual for the outdoor unit CAUTION Keep indoor unit outdoor unit power sup...

Page 7: ...ure by changing the initial setting from the remote controller Refer to the section entitled 10 FIELD SETTING Indoor unit Suspension bolt 4 1000 Indoor unit 1050 Suspension bolt pitch Pipe 630 145 Sus...

Page 8: ...Fig 3 2 Check the unit is horizontally level Refer to Fig 4 CAUTION The indoor unit is equipped with a built in drain pump and float switch Verify that it is level by using a level or a water filled...

Page 9: ...either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while wor...

Page 10: ...copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine base...

Page 11: ...rain pipe from sagging space hanging wires every 1 to 1 5 m CAUTION Water pooling in the drainage piping can cause the drain to clog Use the attached drain hose 3 and Metal clamp 1 Insert the drain ho...

Page 12: ...n the water inlet lid add approximately 1000 cc of water gradually and check drainage flow Refer to Fig 16 NOTE Use the drain outlet for maintenance to drain water from the drain pan WHEN ELECTRIC WIR...

Page 13: ...performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed Refer to the installation manual attached to the outdoor unit and...

Page 14: ...g the units Doing so may cause malfunction Remote controller cord Control box Control box lid WIRING DIAGRAM Fig 18 CAUTION After wiring adhere the attached small sealing pad 13 around the wires as sh...

Page 15: ...Observe the notes when wiring to the terminal block for wiring the units Use a round crimp style terminal with insulation sleeve for connection to the terminal block for wiring the units In case it ca...

Page 16: ...be used connect a shielded portion with the grounding terminal for remote controller inside the control box Also connect the ground for the remote control to a grounded metal part 3 For group control...

Page 17: ...able 4 4 When implementing group control When using as a pair unit or as a parent unit for simultaneous operation multi you may simultaneous start stop group control up to 16 unit with the remote cont...

Page 18: ...y and decoration panel 12 TEST OPERATION Refer to the section of FOR THE FOLLOWING ITEMS TAKE SPECIAL CARE DURING CON STRUCTION AND CHECK AFTER INSTALLATION IS FINISHED After finishing the constructio...

Page 19: ...recognized NOTE 2 NOTE 1 In case wired remote controller Press the INSPECTION TEST OPERATION button on remote con troller starts flashing and changes the inspection mode 2 Keep down the ON OFF button...

Page 20: ...function outdoor unit H9 Outdoor air thermistor faulty outdoor unit J3 Discharge pipe thermistor faulty outdoor unit J5 Suction pipe thermistor faulty outdoor unit J6 Heat exchanger thermistor faulty...

Page 21: ...the fan mounted on the outdoor unit may start operation independent of the remote controller operation U5 Transmission error indoor unit remote controller Transmission is improper between the indoor...

Page 22: ...DAPTOR FOR SKY AIR SERIES CONTROL BOX TO BP UNIT INDOOR UNIT WIRED REMOTE CONTROLLER OPTIONAL PARTS NOTE 7 NOTE 7 CONNECTER DISCRIMINATION COLOUR FOR COMPONENTS CONNECTER COLOUR FOR COMPONENTS CONNECT...

Page 23: ...0506 HT 3P156215 4C EM04A076B 00_CV_3P156215 4C fm Page 2 Saturday May 14 2005 10 52 AM...

Reviews: